HTP · Elite FT (EFT) (discontinued)
HTP EFT-55
The HTP EFT-55 is the 55 MBH class model of the retired Elite FT stainless steel fire-tube boiler line: 11,000 to 55,000 BTU/hr input, 51 MBH heating capacity, 125 lb shipping weight and a 5:1 turndown, recorded from the official LP-387 technical table.
Key figures
- Max input
- 55 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 11 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
HTP EFT-55 in practice
The EFT-55 is one of the seven Elite FT heating boilers on HTP's retired Elite FT page. The official LP-387 technical specifications table prints 11,000 to 55,000 BTU/hr input, 51 MBH heating capacity, a 125 lb shipping weight, 2.2 gal of boiler water content and a 17.5" x 32.5" x 17.4" (W x H x D) wall-hung cabinet with 1" copper SWT supply/return and 3/4" NPTF gas inlet.
The Elite FT is a stainless steel vertical fire-tube, down-fired condensing boiler with a 5:1 turndown, the 926 SIT control (outdoor reset, DHW indirect priority, cascade up to eight boilers, 0-10V BMS input) and Category IV sealed-combustion venting in PVC, CPVC, polypropylene or stainless steel. The retired page prints 'up to a 95.1% AFUE rating with up to a 10 to 1 turndown ratio' and SCAQMD Rule 1146.2 compliance; the 5:1 submittal prints up to 96.3% AFUE for the smaller models. The heat exchanger carries a 12-year limited warranty.
The Elite FT line is retired: HTP's discontinued-products index lists 'Elite FT Heating Boiler' and the EFT documents page remains as archived support. Boilers.ca records it with productStatus 'discontinued' and canadianStatus 'unknown'; no official Canadian sales statement was found. Service an installed unit with a licensed contractor against LP-387.
Best suited to
- Identifying a retired Elite FT boiler already installed
- Retrieving the official LP-387/LP-657 documentation for an existing unit
- Replacement planning with the existing input and capacity known
Applicability and support
- Model number
- EFT-55
- Canadian availability
- unknown
- Production status
- discontinued
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by HTP. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Input rate, minimum | 11 MBH | 11,000 BTU/hr per LP-387. |
| Input rate, maximum | 55 MBH | 55,000 BTU/hr per LP-387. |
| Output | ||
| Heating capacity | 51 MBH | As printed in the LP-387 technical specifications table (367* for the 399 as printed; *N/A Energy Guide). |
| Venting and air | ||
| Venting | 3" (200 ft combined) | Category IV sealed-combustion direct vent; PVC, CPVC, polypropylene or stainless steel per LP-387. The 5:1 line prints a 200 ft combined limit (150 ft on the 285). |
| Physical and connections | ||
| Shipping weight | 125 lb | As printed in the LP-387 technical specifications table. |
| Boiler water content | 2.2 gal | As printed in the LP-387 technical specifications table. |
| Dimensions (W x H x D) | 17.5" x 32.5" x 17.4" | As printed in the LP-387 technical specifications table. |
| Gas inlet connection | 3/4" NPTF | As printed in the LP-387 technical specifications table; gas supply pressure NG/LP 3.5"-14" WC. |
| Water pressure MAWP / relief | 30 psi / 30 psi | As printed in LP-387 (30 psi for EFT-55 through 199; 80 psi for EFT-285/399). |
| Heat exchanger | Stainless steel vertical fire tube (ASME 'H' stamped, National Board listed) | LP-392 prints 'All Stainless Steel ASME H Stamped Construction'; LP-391 prints 439 stainless steel for the 5:1 models. |
| Operating limits and other | ||
| CH supply/return connection | 1" copper SWT | As printed in the LP-387 technical specifications table; top and bottom supply/return connections (bottom only on EFT-55/80/110). |
| Turndown | 5:1 | 5:1 per LP-392/LP-391 for the EFT-55 through EFT-199 generation. |
| Control | 926 SIT control with 2-line/20-character LCD and LED indicators | Outdoor reset, DHW indirect priority, cascade up to 8 boilers, 0-10V BMS input, last 10 fault codes with date/time per LP-392. |
| Warranty | 12-year limited heat-exchanger warranty | LP-392/LP-391 print a 12 year limited warranty; the retired product page prints a twelve year warranty. |
Manuals
- HTP Elite FT Installation and Operation Manual — LP-387 Rev. 011 Rel. 009 (2.19.21)LP-387 Rev. 011 (2.19.21) · 2021-02-19
- HTP Elite FT Submittal Sheet for 5:1 turndown models — LP-392 Rev. 7.27.20LP-392 (7.27.20) · 2020-07-27
Frequently asked questions
What is the input range of the EFT-55?
LP-387 prints 11,000 to 55,000 BTU/hr with 51 MBH heating capacity.
What is the EFT-55 turndown?
5:1 per the LP-392/LP-391 specification documents for the EFT-55 through EFT-199 generation.
Is the Elite FT still sold?
No — HTP's discontinued-products index lists the Elite FT Heating Boiler; the pages and manuals remain for support.
Questions about the HTP EFT-55?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- HTP — Elite FT Heating Boiler (retired page, model table) · accessed September 9, 2026
- HTP — Elite FT documents · accessed September 9, 2026
- Elite FT Installation and Operation Manual, LP-387 Rev. 011 (2.19.21) · accessed September 9, 2026
- Elite FT Submittal Sheet (5:1 models), LP-392 · accessed September 9, 2026
- HTP — Discontinued Products index · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.