Lochinvar · Knight Wall Mount (WHB)
Lochinvar Knight WHB285
The Knight WHB285 is the 285 MBH wall-hung Knight: 28.5 to 285 MBH input at 95% AFUE with 264 MBH DOE capacity, 4" venting available to 100 equivalent feet and 1-1/4" connections.
Key figures
- Max input
- 285 MBH
- Max CSA output
- —
- AFUE
- 95 %
- Min input
- 28.5 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Knight WHB285 in practice
The WHB285 sits near the top of the wall-hung Knight line with 28.5 to 285 MBH of input, 264 MBH of DOE heating capacity and a 230 MBH AHRI net rating at 95% AFUE. It is a candidate for large homes and light-commercial loads rather than an average house, because its minimum fire of 28.5 MBH is already a substantial part-load.
Water connections stay at 1-1/4" with a 1/2" gas connection and water content of 4.9 gallons. The venting table offers a choice: 3" pipe to 50 equivalent feet or 4" to 100, which lets a long vent route run in 4". As a heating-only boiler it is paired with an indirect tank such as the Squire for domestic hot water.
Best suited to
- Very large homes and small commercial spaces with loads above 200 MBH
- Long vent routes that the 4" allowance (100 equivalent ft) can reach
- High-recovery indirect-tank systems driven by the SMART SYSTEM
Applicability and support
- Model number
- WHB285L
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 28.5 MBH | Per the I&O ratings table. |
| Heating input, maximum | 285 MBH | Per the I&O ratings table. |
| Output | ||
| DOE heating capacity | 264 MBH | DOE heating capacity per the I&O ratings table. |
| AHRI net water rating | 230 MBH | Net AHRI rating based on a piping and pickup allowance of 1.15. |
| Efficiency | ||
| Efficiency (AFUE) | 95 % | 95% AFUE per the I&O ratings table. |
| Domestic hot water | ||
| Domestic hot water | Heating-only boiler | Pairs with the Squire indirect water heater or another indirect tank; the Knight is heating-only. |
| Venting and air | ||
| Venting | Category IV sealed combustion; PVC, CPVC, polypropylene or stainless steel | In Canada, plastic venting must be a ULC S636-certified system. |
| Max. equivalent vent/air length, 3" | 50 ft | Table 3D (air intake/vent piping sizes), I&O manual. |
| Max. equivalent vent/air length, 4" | 100 ft | Table 3D (air intake/vent piping sizes), I&O manual. |
| Physical and connections | ||
| Water content | 4.9 gal | Per the I&O ratings table. |
| Space-heating water connections | 1-1/4" | Per the I&O ratings table. |
| Gas connection | 1/2" | Per the I&O ratings table. |
Manuals
Alerts documented for this model
- Gas Pressure SW
- Flow Switch/LWCO
- Air Pressure SW
- Too Many Recyclings
- Anti-cycling
- Flame Fail Ign
- Flame Sequence
- Outlet ARHL
- Outlet MRHL
- Fan Speed
- Inlet, Outlet, or Flue Sensor Fault
- AUX Contact Sw
- Outlet Temp Diff
- Fatal Error
- Memory Error
- Flue Temp High / Flue Temp Limit
- Delta T High / Delta T Limit
- Outlet Temp High / Outlet Temp Limit
- Low 24 vac
- Watch Dog Error
- Write EEProm
- CRC Parameters
- No Error Stored
Frequently asked questions
What venting options does the WHB285 have?
Table 3D in the I&O manual lists 3" venting to 50 equivalent feet or 4" to 100 equivalent feet for the 285 size.
Is the WHB285 suitable for an average house?
Rarely. Its 28.5 MBH minimum fire is high for a typical home's shoulder-season load, so the boiler would spend much of the year near its minimum. A heat-loss calculation should justify the 285 MBH ceiling.
Questions about the Lochinvar Knight WHB285?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
Sources and verification
- Lochinvar — Knight Fire Tube Wall Mount (WHB055L) model page · accessed September 7, 2026
- Knight Wall Hung Fire Tube (WHB055-399) I&O Manual, Rev T · Rev T · accessed September 7, 2026
Facts checked September 7, 2026. Last updated September 7, 2026. Technical reviewer: not yet assigned.