Lochinvar · Knight Wall Mount (WHB)
Lochinvar Knight WHB399
The Knight WHB399 tops the wall-hung Knight line at 399 MBH of input and 377 MBH DOE capacity, rated by 94.4% thermal efficiency rather than AFUE, with 1-1/2" connections and 4" venting.
Key figures
- Max input
- 399 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 39.9 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Knight WHB399 in practice
The WHB399 is the largest wall-hung Knight and the only one whose rating is not an AFUE figure: the I&O ratings table rates it 94.4% thermal efficiency instead, with 377 MBH of DOE heating capacity and a 328 MBH AHRI net water rating at 399 MBH of maximum input. Minimum input is listed at 39.9 MBH for Series 120/121 units, with a 79.8 MBH minimum noted for Series 100-111.
Everything about the 399 is scaled up: water content reaches 6.5 gallons, heating connections step to 1-1/2" with a 3/4" gas connection, and venting is 4" to 100 equivalent feet. It remains a heating-only boiler paired with an indirect tank, and its application is large buildings rather than the typical detached home.
Best suited to
- Large residential and light-commercial heating loads up to 399 MBH
- Projects whose piping and gas supply are planned for 1-1/2" and 3/4" connections
- Systems able to commit to 4" venting to 100 equivalent feet
Applicability and support
- Model number
- WHB399L
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 39.9 MBH | Minimum input shown is for Series 120/121 units; the I&O table notes Series 100-111 minimum input is 79.8 MBH. |
| Heating input, maximum | 399 MBH | Minimum input shown is for Series 120/121 units; the I&O table notes Series 100-111 minimum input is 79.8 MBH. |
| Output | ||
| DOE heating capacity | 377 MBH | DOE heating capacity per the I&O ratings table. |
| AHRI net water rating | 328 MBH | Net AHRI rating based on a piping and pickup allowance of 1.15. |
| Efficiency | ||
| Efficiency (thermal) | 94.4 % | The WHB399 is rated by thermal efficiency (94.4%) rather than AFUE, per the I&O ratings table. |
| Domestic hot water | ||
| Domestic hot water | Heating-only boiler | Pairs with the Squire indirect water heater or another indirect tank; the Knight is heating-only. |
| Venting and air | ||
| Venting | Category IV sealed combustion; PVC, CPVC, polypropylene or stainless steel | In Canada, plastic venting must be a ULC S636-certified system. |
| Max. equivalent vent/air length, 4" | 100 ft | Table 3D (air intake/vent piping sizes), I&O manual. |
| Physical and connections | ||
| Water content | 6.5 gal | Per the I&O ratings table. |
| Space-heating water connections | 1-1/2" | Per the I&O ratings table. |
| Gas connection | 3/4" | Per the I&O ratings table. |
Manuals
Alerts documented for this model
- Gas Pressure SW
- Flow Switch/LWCO
- Air Pressure SW
- Too Many Recyclings
- Anti-cycling
- Flame Fail Ign
- Flame Sequence
- Outlet ARHL
- Outlet MRHL
- Fan Speed
- Inlet, Outlet, or Flue Sensor Fault
- AUX Contact Sw
- Outlet Temp Diff
- Fatal Error
- Memory Error
- Flue Temp High / Flue Temp Limit
- Delta T High / Delta T Limit
- Outlet Temp High / Outlet Temp Limit
- Low 24 vac
- Watch Dog Error
- Write EEProm
- CRC Parameters
- No Error Stored
Frequently asked questions
Is the WHB399 rated 95% AFUE like the smaller Knights?
No. The I&O ratings table rates the WHB399 by thermal efficiency (94.4%) rather than AFUE; the 055-285 sizes carry the 95% AFUE figures.
What is the WHB399's minimum input?
The I&O table prints 39.9 MBH for Series 120/121 units and notes that Series 100-111 units have a 79.8 MBH minimum input.
Questions about the Lochinvar Knight WHB399?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- Lochinvar — Knight Fire Tube Wall Mount (WHB055L) model page · accessed September 7, 2026
- Knight Wall Hung Fire Tube (WHB055-399) I&O Manual, Rev T · Rev T · accessed September 7, 2026
Facts checked September 7, 2026. Last updated September 7, 2026. Technical reviewer: not yet assigned.