Lochinvar · Noble Fire Tube (NKB/NKC/NCF)
Lochinvar Noble NKC199
The Noble NKC199 is the top Noble wall-hung combi: 19.9 to 199 MBH space-heating input at 95.0% AFUE with 185 MBH DOE capacity, DHW on demand through 3/4" connections.
Key figures
- Max input
- 199 MBH
- Max CSA output
- —
- AFUE
- 95 %
- Min input
- 19.9 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Noble NKC199 in practice
The NKC199 is the largest Noble combi on a wall: 19.9 to 199 MBH of space-heating input with 185 MBH of DOE heating capacity and a 161 MBH AHRI net rating at 95.0% AFUE. For a large home or small multi-suite building whose load approaches 200 MBH and whose owners want one appliance for heat and hot water, this is the wall-hung option at the top of the combi line.
Its water content reaches 2.7 gallons, connections are 1" NPT for space heating with 3/4" for DHW and a 1/2" gas connection, and the 2" vent allowance shortens to 50 equivalent feet while 3" reaches 100. The combi's DHW mode is managed by the SMART CONTROL, which reports text-name faults, and Lochinvar's residential page sells the Noble combis as Epic in Canada.
Best suited to
- Large homes and small multi-suite buildings with loads near 199 MBH
- One-appliance heat and hot water without a tank or second appliance
- Projects able to run 3" venting to 100 equivalent feet
Applicability and support
- Model number
- NKC199L
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 19.9 MBH | Per the I&O ratings table. |
| Heating input, maximum | 199 MBH | Per the I&O ratings table. |
| Output | ||
| DOE heating capacity | 185 MBH | DOE heating capacity per the I&O ratings table. |
| AHRI net water rating | 161 MBH | Net AHRI rating based on a piping and pickup allowance of 1.15. |
| Efficiency | ||
| Efficiency (AFUE) | 95 % | 95.0% AFUE per the I&O ratings table. |
| Domestic hot water | ||
| Domestic hot water | On demand from the combi's DHW circuit | Combi models produce DHW directly; the I&O ratings list 3/4" DHW water connections for combi units. |
| Venting and air | ||
| Venting | Category IV sealed combustion; PVC, CPVC, polypropylene or stainless steel | In Canada, plastic venting must be a ULC S636-certified system. |
| Max. equivalent vent/air length, 2" | 50 ft | Table 3D (air intake/vent piping sizes), I&O manual. |
| Max. equivalent vent/air length, 3" | 100 ft | Table 3D (air intake/vent piping sizes), I&O manual. |
| Physical and connections | ||
| Water content | 2.7 gal | Per the I&O ratings table. |
| Space-heating water connections | 1" NPT | Noble ratings: NPT connections are used on combi units, sweat connections on the boiler. |
| DHW water connections | 3/4" | Combi-only, per the I&O ratings table (NPT = combi). |
| Gas connection | 1/2" | Per the I&O ratings table. |
Manuals
Alerts documented for this model
- Memory Error
- Fan Speed
- LWCO
- Flame Sequence
- Outlet ARHL
- Air Pressure Switch
- AUX Limit Fault
- Flame Fail: Running
- Flame Fail: Ignition
- Flue Temp Limit
- Flue Temp High
- Outlet MRHL
- Outlet Temp High
- Outlet Temp DIFF
- Flue Sensor Fault
- Outlet Sensor Fault
- Inlet Sensor Fault
- Set Point Met
- Anti-Cycling
- Delta T High
- Low Voltage
- No Flue Temp Change
- Combi Sensor Fault (Combi Only)
- Lockout Inlet Sensor Fault
- Outdoor Sensor Missing
- No Hot Water at Faucets (Combi Only)
- DHW Water is not Hot Enough (Combi Only)
- Combi Boiler is Running but Does Not Supply Heated Water to Space Heating System (Combi Only)
- Space Heating System Heat Emitters Get Hot During a DHW Draw and the Combi Boiler does not Provide Hot Enough Domestic Hot Water (Combi Only)
- Lockout! Water Press Switch
Frequently asked questions
What are the NKC199's ratings?
19.9 to 199 MBH of space-heating input with 185 MBH DOE heating capacity and a 161 MBH AHRI net rating at 95.0% AFUE, per the Noble I&O ratings table.
How does the NKC199 venting compare with the smaller combis?
The 2" allowance drops to 50 equivalent feet at the 199 size (from 100 on the 110 and 60 on the 150), while 3" venting stays at 100 equivalent feet.
Questions about the Lochinvar Noble NKC199?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Lochinvar Noble NKC150 vs NKC199Comparison
- IBC SFC 199-1 Superflow vs Lochinvar Noble NKC199Comparison
- Lochinvar Noble NKB080Same series
- Lochinvar Noble NKB110Same series
- Lochinvar Noble NKB150Same series
- Lochinvar Noble NKB199Same series
- Lochinvar Noble NKC110Same series
- Lochinvar Noble NKC150Same series
- Lochinvar Noble NCF110Same series
- Lochinvar Noble NCF150Same series
- Lochinvar Noble NCF199Same series
- Noble Fire Tube (NKB/NKC/NCF) series hub
- Buying guide
Sources and verification