Crown Phantom II PHTM2180H

The Crown Phantom II PHTM2180H is the largest Phantom II heat-only boiler: 20 to 180 MBH input at 95.0% AFUE with 169 MBH DOE heating capacity and a 147 MBH net AHRI rating, in the same 132 lb large cabinet as the 2150H.

CurrentCanadian status unknown

Key figures

Max input
180 MBH
Max CSA output
—
AFUE
95 %
Min input
20 MBH
Natural gasPropaneHeating-onlyresidential

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Crown Phantom II PHTM2180H in practice

The PHTM2180H tops the Phantom II heat-only range at 20–180 MBH input with 169 MBH DOE heating capacity and a 147 MBH net AHRI water rating at 95.0% AFUE (product ratings table; I&O manual 110332-07, 9/25). Like every Phantom II it is a stainless steel modulating condensing boiler with direct spark ignition, the gas-adaptive 'PHTM II' control and 10:1 modulation, and it is heating-only.

It shares the large 20.4 × 17.8 × 29.8 inch cabinet with the 2150H at the same 132 lb shipping weight and 1.0 gal of water content, connecting on 1" sweat supply/return with 1/2" MPT gas at 50 psig MAWP. Venting is 2" to 70 ft or 3" with increaser to 135 ft, with the LP-above-8,000-ft limit of 50 ft equivalent applying to this size. Its 20 MBH minimum fire means the heat-loss calculation must genuinely support the size — a mid-size home will modulate better on the 2120H or 2150H.

Best suited to

  • Large homes and small multi-suite plants whose calculated load approaches 180 MBH
  • High-demand indirect-tank systems within the Phantom II heat-only ceiling
  • Projects wanting the full Phantom II family capacity at 95.0% AFUE

Applicability and support

Model number
PHTM2180H
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Crown Boiler Co.. Units are shown with every value; notes flag conflicting sources or missing figures.

Crown Phantom II PHTM2180H specifications
SpecificationValueNote
Input
Input, minimum20 MBHMinimum input per the space-heating ratings table (product page; Table 3-1).
Input, maximum180 MBHMaximum input per the space-heating ratings table (product page; Table 3-1).
Output
DOE heating capacity169 MBHDOE heating capacity per the product ratings table.
Net AHRI water rating147 MBHNet AHRI water rating based on a piping and pickup allowance of 1.15, per the product ratings table.
Efficiency
Efficiency (AFUE)95 %95.0% AFUE per the product ratings table.
Domestic hot water
Domestic hot waterHeating-only boiler — domestic hot water comes from a separate indirect tank or water heater
Venting and air
Max. equivalent vent length, 2"70 ft2" standard venting, 2.5 ft minimum; derated 6–9% at maximum length. See I&O manual Table 3-3.
Max. equivalent vent length, 3"135 ft3" venting with increaser, 2.5 ft minimum; derated 1–5% at maximum length. See I&O manual Table 3-3.
Physical and connections
Boiler water content1 galWater content per the I&O manual specifications.
Shipping weight132 lbApproximate shipping weight per the product ratings table.
Dimensions (D × W × H)20.4" × 17.8" × 29.8"Depth × width × height per the product dimensions table and the I&O manual (Table 3-2).
Heating water connections1" sweatSupply and return 1" sweat per the product page and I&O manual (Table 3-2).
Gas connection1/2" MPTGas connection 1/2" MPT per the product page.
Electrical
Electrical120 VAC, 60 Hz, 1-phase, 1.8 ABoiler and pump draw per the I&O manual electrical requirements.
Operating limits and other
Turndown ratio10:1Product-page copy: modulating burner with 10:1 turndown ratio.
Maximum allowable working pressure (MAWP)50 psig50 psig maximum allowable working pressure per the I&O manual (Table 3-2).
ControlGas-adaptive 'PHTM II' control with rate-based temperature resetRate-based reset needs no outdoor sensor; PAT gas-adaptive technology; H/E-code diagnostics per the I&O manual.
FuelNatural gas or LPShips as a natural gas boiler, field convertible to LP with no conversion kit required (product page). NG inlet 2.5–14" w.c.; LP inlet 8–14" w.c.

Frequently asked questions

What are the PHTM2180H's ratings?

20–180 MBH input, 169 MBH DOE heating capacity, a 147 MBH net AHRI water rating and 95.0% AFUE per the product ratings table.

How does the PHTM2180H compare with the PHTM2150H?

Both use the 20.4 × 17.8 × 29.8 inch cabinet at 132 lb, but the 2180H fires to 180 MBH maximum input against the 2150H's 150 MBH — 169 MBH DOE capacity and a 147 MBH net AHRI rating against 141 and 123 MBH.

Is the PHTM2180H a good fit for an average house?

Only if the heat-loss calculation supports it: its 20 MBH minimum fire is the highest minimum in the heat-only range, so a low-load home would spend more time at minimum fire instead of modulating.

Questions about the Crown Phantom II PHTM2180H?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 8, 2026. Last updated September 8, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate