Skip to content
Boilers.caby ROMA Heating & Cooling

Viessmann · Vitogas 050 (ECD / ECV / RS)

Viessmann Vitogas 050 RS-14

The Vitogas 050 RS-14 is the largest commercial RS boiler: 1050 MBH full-load input (308 kW), 893 MBH output and 85% combustion efficiency with a 14-section block.

DiscontinuedHistorically in Canada

Key figures

Max input
—
Max CSA output
—
AFUE
—
Min input
—
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Viessmann Vitogas 050 RS-14 in practice

The RS-14 tops the RS range at 1050 MBH (308 kW) full-load input, 710 MBH (208 kW) partial load and 893 MBH (261 kW) full-load output at 85% combustion efficiency. It is built from 14 cast-iron sections with 13 burners and holds 35 USG of boiler water at 60 psig maximum operating pressure.

At 2,138 lb (972 kg) it measures 1,582 mm (62¼ in) wide with the series' 883 mm depth and 1366 mm height, connecting through 2 in. supply and return, 1¼ in. gas and a 14 in. vent pipe collar.

Best suited to

  • Existing RS-14 installations needing printed ratings
  • The largest Vitogas 050 commercial loads at 1050 MBH full-load input
  • Documentation for 14-section RS builds

Applicability and support

Model number
RS-14
Canadian availability
historical
Production status
discontinued
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Viessmann. Units are shown with every value; notes flag conflicting sources or missing figures.

Viessmann Vitogas 050 RS-14 specifications
SpecificationValueNote
Input
CSA input, full load1,050 MBH308 kW, per the technical data manual
CSA input, partial load710 MBH208 kW; two-stage boilers only.
Output
CSA output, full load893 MBH261 kW; supply 167°F / return 140°F.
CSA output, partial load604 MBH177 kW; two-stage boilers only.
Efficiency
Combustion efficiency85 %Printed for all three RS sizes.
Venting and air
Vent pipe collar14 inOutside diameter per the technical data manual.
Physical and connections
Weight (with insulation, burners and packaging)2,138 lb972 kg
Depth883 mm34¾ in; total depth with controls 1195 mm (47 in).
Width1,582 mmTotal width per the technical data manual.
Height1,366 mm53¾ in; 1531 mm with control in operating position, 1867 mm for servicing.
Operating limits and other
FuelNatural gas or propane3.5 in. w.c. manifold pressure NG at full load; propane not available in two-stage configuration.
Cast iron sections1413 burners.
Boiler water content35 USG
Maximum operating pressure60 psig414 kPa.
Boiler supply / return2 in. male threadGas supply 1¼ in.; boiler drain ¾ in.

Frequently asked questions

What is the RS-14 rated at?

1050 MBH (308 kW) full-load input, 710 MBH partial load, 893 MBH (261 kW) full-load output and 85% combustion efficiency, with 14 sections and 13 burners.

How much does the RS-14 weigh?

2,138 lb (972 kg) with insulation, burners and packaging, with 35 USG of boiler water content.

Can the RS-14 run on propane?

The technical data manual prints propane manifold pressure for full-load operation but notes propane is not available in the two-stage configuration; partial-load values apply to two-stage boilers only.

Questions about the Viessmann Vitogas 050 RS-14?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate