The Vitogas 050 RS-8 is the smallest commercial RS boiler: 550 MBH full-load input (161 kW), 468 MBH output and 85% combustion efficiency, two-stage fired with an 8-section block.

DiscontinuedHistorically in Canada

Key figures

Max input
—
Max CSA output
—
AFUE
—
Min input
—
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Viessmann Vitogas 050 RS-8 in practice

The RS-8 is an atmospheric cast-iron commercial boiler rated 550 MBH (161 kW) full-load input, 372 MBH (109 kW) at partial load, and 468 MBH (137 kW) full-load output at a printed 85% combustion efficiency. It is built from eight cast-iron sections with seven burners and holds 20 USG of boiler water at 60 psig maximum operating pressure.

At 1,280 lb (582 kg) it measures 883 x 921 mm (34¾ x 36¼ in) with a 1366 mm (53¾ in) height, and it connects through 2 in. male-thread supply and return, a 1 in. gas connection and a 10 in. vent pipe collar. The RS series uses single- or two-stage burners per the technical data manual.

Best suited to

  • Existing RS-8 installations needing printed ratings
  • Commercial loads from 550 MBH with two-stage firing
  • Documentation for the entry RS size

Applicability and support

Model number
RS-8
Canadian availability
historical
Production status
discontinued
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Viessmann. Units are shown with every value; notes flag conflicting sources or missing figures.

Viessmann Vitogas 050 RS-8 specifications
SpecificationValueNote
Input
CSA input, full load550 MBH161 kW, per the technical data manual
CSA input, partial load372 MBH109 kW; two-stage boilers only.
Output
CSA output, full load468 MBH137 kW; supply 167°F / return 140°F.
CSA output, partial load316 MBH93 kW; two-stage boilers only.
Efficiency
Combustion efficiency85 %Printed for all three RS sizes.
Venting and air
Vent pipe collar10 inOutside diameter per the technical data manual.
Physical and connections
Weight (with insulation, burners and packaging)1,280 lb582 kg
Depth883 mm34¾ in; total depth with controls 1195 mm (47 in).
Width921 mmTotal width per the technical data manual.
Height1,366 mm53¾ in; 1531 mm with control in operating position, 1867 mm for servicing.
Operating limits and other
FuelNatural gas or propane3.5 in. w.c. manifold pressure NG at full load; propane not available in two-stage configuration.
Cast iron sections87 burners.
Boiler water content20 USG
Maximum operating pressure60 psig414 kPa.
Boiler supply / return2 in. male threadGas supply 1 in.; boiler drain ¾ in.

Frequently asked questions

What is the RS-8 rated at?

550 MBH (161 kW) full-load input, 372 MBH partial load, 468 MBH (137 kW) full-load output and 85% combustion efficiency, with eight cast-iron sections and seven burners.

Is the RS-8 a two-stage boiler?

The RS series is documented with single- or two-stage burners; partial-load values printed in the technical data manual apply to two-stage boilers only.

Is the Vitogas 050 RS-8 still sold?

No. The Vitogas 050 line is discontinued and documented under Viessmann Canada's historic manuals.

Questions about the Viessmann Vitogas 050 RS-8?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.