Viessmann
Viessmann Vitogas 050 ECD-65
- Input
- —
- Output (max)
- —
- AFUE
- 83.7 %
The Vitogas 050 ECD-65 is the smallest ECD atmospheric cast-iron boiler: 65 MBH input (19 kW), 54 MBH output and 83.7% AFUE in a three-section chassis.
Canada-wide gas boiler information · On-site service in Greater Vancouver, BC
Boilers.ca is a brand of ROMA Heating & Cooling · Licensed gas contractor LGA0202903
Viessmann · Series
The Vitogas 050 is a discontinued atmospheric cast-iron gas boiler line kept in Viessmann Canada's historic manuals: the residential ECD, ECD-S and ECV variants in eight sizes from 65 to 200 MBH, and the commercial RS variant in three sizes from 550 to 1050 MBH.
Series facts
83.0-83.7% AFUE on the ECD/ECD-S residential models and 83.1% on the ECV; the commercial RS models print 85% combustion efficiency.
The Vitogas 050 is a natural gas or propane-fired cast-iron hot-water boiler with an atmospheric burner, sold in Canada in several variants. The residential ECD, ECD-S and ECV series share eight sizes — 65, 80, 100, 115, 140, 155, 180 and 200 — covering 65 to 200 MBH (19 to 59 kW) input. The ECD and ECD-S print 83.0-83.7% AFUE; the ECV prints 83.1% AFUE across all eight sizes. The commercial RS series has three sizes — RS-8, RS-11 and RS-14 — covering 550 to 1050 MBH (161 to 308 kW) with a printed 85% combustion efficiency and single- or two-stage firing.
The residential variants split by trim and venting. ECD and ECD-S are chimney-vented with a draft hood, and Viessmann's data sheet notes each ECD-S ships with a FieldControls vent damper to meet the minimum AFUE; the ECV uses a 3 in. vent collar with a 20 ft maximum equivalent vent run. The ECD-S cabinet stands taller (43 in. / 1092 mm on the 65-155 sizes and 46 in. / 1168 mm on the 180/200) than the ECD and ECV. All residential sizes share 50 psig maximum operating pressure, 1¼ in. supply and return connections and ½ in. gas connections.
The RS commercial models are built from 8, 11 and 14 cast-iron sections with 7, 10 and 13 burners respectively, at 60 psig maximum operating pressure and 2 in. supply and return connections. The whole line is discontinued and documented under Viessmann Canada's historic manuals, including the ECD technical data manual (doc 5167 444 v1.4, 01/2008), the ECD-S technical data sheet, the ECV technical data manual (doc 5167 449 v1.3, 01/2008) and the RS technical data manual (v1.2, 01/2004).
Highlights
Models
One canonical page per model with input, output and efficiency kept separate.
Viessmann
The Vitogas 050 ECD-65 is the smallest ECD atmospheric cast-iron boiler: 65 MBH input (19 kW), 54 MBH output and 83.7% AFUE in a three-section chassis.
Viessmann
The Vitogas 050 ECD-80 is the second ECD size: 80 MBH input (23 kW), 66 MBH output and 83.5% AFUE in the same compact three-section chassis as the ECD-65.
Viessmann
The Vitogas 050 ECD-100 is a four-section ECD boiler: 100 MBH input (29 kW), 83 MBH output and 83.5% AFUE with a 6 in. vent collar.
Viessmann
The Vitogas 050 ECD-115 is the larger of the two four-section ECD sizes: 115 MBH input (34 kW), 95 MBH output and 83.5% AFUE.
Viessmann
The Vitogas 050 ECD-140 is a five-section ECD boiler: 140 MBH input (41 kW), 116 MBH output and 83.5% AFUE with a 7 in. vent collar.
Viessmann
The Vitogas 050 ECD-155 is the larger five-section ECD size: 155 MBH input (45 kW), 129 MBH output and 83.4% AFUE.
Viessmann
The Vitogas 050 ECD-180 opens the largest ECD chassis: 180 MBH input (53 kW), 149 MBH output and 83.2% AFUE with six sections.
Viessmann
The Vitogas 050 ECD-200 is the largest ECD boiler: 200 MBH input (59 kW), 166 MBH output and 83.0% AFUE — the lowest printed figure in the range.
Viessmann
The Vitogas 050 ECV-65 is the smallest ECV boiler: 65 MBH input (19 kW), 55 MBH output and 83.1% AFUE with a 3 in. power-vent collar.
Viessmann
The Vitogas 050 ECV-80 is the second ECV size: 80 MBH input (23 kW), 67 MBH output and 83.1% AFUE in the compact three-section chassis.
Viessmann
The Vitogas 050 ECV-100 is a four-section ECV boiler: 100 MBH input (29 kW), 84 MBH output and 83.1% AFUE with a 3 in. vent collar.
Viessmann
The Vitogas 050 ECV-115 is the larger four-section ECV size: 115 MBH input (34 kW), 97 MBH output and 83.1% AFUE.
Viessmann
The Vitogas 050 ECV-140 is a five-section ECV boiler: 140 MBH input (41 kW), 118 MBH output and 83.1% AFUE.
Viessmann
The Vitogas 050 ECV-155 is the larger five-section ECV size: 155 MBH input (45 kW), 131 MBH output and 83.1% AFUE.
Viessmann
The Vitogas 050 ECV-180 opens the largest ECV chassis: 180 MBH input (53 kW), 151 MBH output and 83.1% AFUE with six sections.
Viessmann
The Vitogas 050 ECV-200 is the largest ECV boiler: 200 MBH input (59 kW), 168 MBH output and 83.1% AFUE with a 3 in. power-vent collar.
Viessmann
The Vitogas 050 RS-8 is the smallest commercial RS boiler: 550 MBH full-load input (161 kW), 468 MBH output and 85% combustion efficiency, two-stage fired with an 8-section block.
Viessmann
The Vitogas 050 RS-11 is the mid-size commercial RS boiler: 800 MBH full-load input (234 kW), 680 MBH output and 85% combustion efficiency with an 11-section block.
Viessmann
The Vitogas 050 RS-14 is the largest commercial RS boiler: 1050 MBH full-load input (308 kW), 893 MBH output and 85% combustion efficiency with a 14-section block.
| Specification | Viessmann Vitogas 050 ECD-65 | Viessmann Vitogas 050 ECD-80 | Viessmann Vitogas 050 ECD-100 | Viessmann Vitogas 050 ECD-115 | Viessmann Vitogas 050 ECD-140 | Viessmann Vitogas 050 ECD-155 | Viessmann Vitogas 050 ECD-180 | Viessmann Vitogas 050 ECD-200 | Viessmann Vitogas 050 ECV-65 | Viessmann Vitogas 050 ECV-80 | Viessmann Vitogas 050 ECV-100 | Viessmann Vitogas 050 ECV-115 | Viessmann Vitogas 050 ECV-140 | Viessmann Vitogas 050 ECV-155 | Viessmann Vitogas 050 ECV-180 | Viessmann Vitogas 050 ECV-200 | Viessmann Vitogas 050 RS-8 | Viessmann Vitogas 050 RS-11 | Viessmann Vitogas 050 RS-14 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| input-min | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| input-max | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| output-max | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| Efficiency (AFUE) | 83.7 % | 83.5 % | 83.5 % | 83.5 % | 83.5 % | 83.4 % | 83.2 % | 83 % | 83.1 % | 83.1 % | 83.1 % | 83.1 % | 83.1 % | 83.1 % | 83.1 % | 83.1 % | — | — | — |
| turndown | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| vent-max-3 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| vent-max-2 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| Weight (with insulation, burners and packaging) | 233 lb | 233 lb | 285 lb | 285 lb | 345 lb | 345 lb | 423 lb | 423 lb | 243 lb | 243 lb | 293 lb | 293 lb | 364 lb | 364 lb | 430 lb | 430 lb | 1,280 lb | 1,709 lb | 2,138 lb |
Read the full comparison: Viessmann Vitogas 050 ECD-65 vs ECD-80 →
Read the full comparison: Viessmann Vitogas 050 ECD-140 vs ECD-155 →
Read the full comparison: Viessmann Vitogas 050 ECD-180 vs ECD-200 →
Read the full comparison: Viessmann Vitogas 050 RS-8 vs RS-11 →
Error codes and alerts
No alerts documented for this series yet.
Manuals
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Services for Viessmann boilers
They are trim and venting variants of the same eight-size residential line. ECD and ECD-S are chimney-vented with a draft hood — ECD-S ships with a FieldControls vent damper — while the ECV uses a 3 in. vent collar with a 20 ft maximum equivalent vent run and prints a uniform 83.1% AFUE.
The residential variants ran 65, 80, 100, 115, 140, 155, 180 and 200 (65 to 200 MBH input). The commercial RS series ran RS-8, RS-11 and RS-14 at 550, 800 and 1050 MBH full-load input.
No. It is an atmospheric, non-condensing cast-iron boiler vented through a chimney. Viessmann Canada's condensing gas boilers are the Vitodens and Vitocrossal lines.
All Vitogas 050 documents live under Viessmann Canada's historic manuals downloads; the ECD, ECD-S, ECV and RS technical data manuals are linked directly on this record.
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.