Lochinvar · Copper-Fin (CBN/CHN)
Lochinvar Copper-Fin Atmospheric CBN315
The Copper-Fin Atmospheric CBN315 is the entry size of the line: 157.5 to 315 MBH input with 258 MBH gross output and a 224 MBH AHRI net rating at 82.0% thermal efficiency, on 2" water and 3/4" gas connections with an 8" Category I vent.
Key figures
- Max input
- 315 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 157.5 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Copper-Fin Atmospheric CBN315 in practice
The CBN315 opens the four-size atmospheric Copper-Fin line. The I&O ratings table lists 157.5 to 315 MBH input, 258 MBH gross output and a 224 MBH AHRI net water rating at 82.0% thermal efficiency, with 1.2 gallons of water content, and the CBA-Sub-08 submittal prints the same input, output, net rating and 82.0% efficiency with a 245 lb shipping weight and 8" vent.
It is a conventional negative-draft Category I appliance: the built-in draft diverter means no additional external draft hood is required, and Type B double-wall vent is used. Firing is two-stage high/low through a two-stage solid state temperature control with two-stage intermittent electronic ignition (M9 standard), and the gasketless ASME copper finned-tube heat exchanger is rated 160 psi working pressure. The submittal prints a 10-year limited heat-exchanger warranty, and Lochinvar's Canada English page is identical to the United States page.
Best suited to
- Commercial loads at the bottom of the atmospheric Copper-Fin range, near 315 MBH
- Buildings with an existing Category I Type B chimney or vertical vent
- Systems that can use two-stage high/low fire instead of full modulation
Applicability and support
- Model number
- CBN315
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 157.5 MBH | Per the I&O ratings table. |
| Heating input, maximum | 315 MBH | Per the submittal sheet and the I&O ratings table. |
| Output | ||
| Gross output | 258 MBH | Gross output per the submittal sheet ratings table. |
| Net AHRI water rating | 224 MBH | Net AHRI rating based on a piping and pickup allowance of 1.15, per the submittal and I&O ratings-table notes. |
| Efficiency | ||
| Efficiency (thermal) | 82 % | 82.0% thermal efficiency printed in the CBA-Sub-08 submittal and on the product page; no AFUE is published. |
| Venting and air | ||
| Vent size | 8" | Per the submittal and I&O ratings tables. |
| Venting | Conventional negative draft (Category I) with built-in draft diverter; Type B double-wall vent | The I&O describes a conventional negative-draft system where the built-in draft diverter means no additional external draft hood is required; the product summary prints Category I, B-VENT material and -0.02 to -0.05 in. w.c. draft. |
| Physical and connections | ||
| Water content | 1.2 gal | Per the I&O ratings table. |
| Space-heating water connections | 2" | 2" NPT on 6-1/4" centers per the CBA-Sub-08 submittal. |
| Gas connection | 3/4" | Per the submittal and I&O ratings tables. |
| Shipping weight | 245 lb | Shipping weight per the submittal sheet ratings table. |
| Dimension A | 29-1/2" | As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal. |
| Dimension B | 32-1/4" | As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal. |
| Dimension C | 21-1/2" | As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal. |
| Dimension D | 16-1/4" | As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal. |
| Operating limits and other | ||
| Firing | Two-stage (high/low fire) | Two-stage intermittent electronic ignition and two-stage solid state temperature control per the CBA-Sub-08 standard features (firing code M9 standard). |
Manuals
Alerts documented for this model
None documented yet.
Frequently asked questions
What are the CBN315's ratings?
157.5 to 315 MBH input, 258 MBH gross output and a 224 MBH AHRI net water rating at 82.0% thermal efficiency, per the CBA-Sub-08 submittal and the I&O ratings table.
How is the CBN315 vented?
Conventionally, as a Category I negative-draft appliance through an 8" Type B double-wall vent; the built-in draft diverter means no additional external draft hood is required.
Questions about the Lochinvar Copper-Fin Atmospheric CBN315?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Lochinvar Copper-Fin Atmospheric CBN360Same series
- Lochinvar Copper-Fin Atmospheric CBN399Same series
- Lochinvar Copper-Fin Atmospheric CBN500Same series
- Lochinvar Copper-Fin Fan Assisted CBN0497Same series
- Lochinvar Copper-Fin Fan Assisted CBN0647Same series
- Lochinvar Copper-Fin Fan Assisted CBN0747Same series
- Lochinvar Copper-Fin Fan Assisted CBN0987Same series
- Lochinvar Copper-Fin Fan Assisted CBN1257Same series
- Lochinvar Copper-Fin Fan Assisted CBN1437Same series
- Lochinvar Copper-Fin Fan Assisted CBN1797Same series
- Lochinvar Copper-Fin Fan Assisted CBN2067Same series
- Lochinvar Copper-Fin II CHN0402Same series
- Lochinvar Copper-Fin II CHN0502Same series
- Lochinvar Copper-Fin II CHN0652Same series
- Lochinvar Copper-Fin II CHN0752Same series
- Lochinvar Copper-Fin II CHN0992Same series
- Lochinvar Copper-Fin II CHN1262Same series
- Lochinvar Copper-Fin II CHN1442Same series
- Lochinvar Copper-Fin II CHN1802Same series
- Lochinvar Copper-Fin II CHN2072Same series
- Copper-Fin (CBN/CHN) series hub
- Buying guide
Sources and verification
- Lochinvar — Copper-fin Atmospheric Commercial Boiler (CBN360) model page · accessed September 9, 2026
- Copper-Fin Atmospheric Boilers (CB 315-500) Submittal Sheet, CBA-Sub-08 · CBA-Sub-08 · accessed September 9, 2026
- Copper-Fin Atmospheric Commercial Boilers I&O Manual, Rev A · Rev A · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.