Lochinvar Copper-Fin Atmospheric CBN315

The Copper-Fin Atmospheric CBN315 is the entry size of the line: 157.5 to 315 MBH input with 258 MBH gross output and a 224 MBH AHRI net rating at 82.0% thermal efficiency, on 2" water and 3/4" gas connections with an 8" Category I vent.

CurrentSold in Canada

Key figures

Max input
315 MBH
Max CSA output
—
AFUE
—
Min input
157.5 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Lochinvar Copper-Fin Atmospheric CBN315 in practice

The CBN315 opens the four-size atmospheric Copper-Fin line. The I&O ratings table lists 157.5 to 315 MBH input, 258 MBH gross output and a 224 MBH AHRI net water rating at 82.0% thermal efficiency, with 1.2 gallons of water content, and the CBA-Sub-08 submittal prints the same input, output, net rating and 82.0% efficiency with a 245 lb shipping weight and 8" vent.

It is a conventional negative-draft Category I appliance: the built-in draft diverter means no additional external draft hood is required, and Type B double-wall vent is used. Firing is two-stage high/low through a two-stage solid state temperature control with two-stage intermittent electronic ignition (M9 standard), and the gasketless ASME copper finned-tube heat exchanger is rated 160 psi working pressure. The submittal prints a 10-year limited heat-exchanger warranty, and Lochinvar's Canada English page is identical to the United States page.

Best suited to

  • Commercial loads at the bottom of the atmospheric Copper-Fin range, near 315 MBH
  • Buildings with an existing Category I Type B chimney or vertical vent
  • Systems that can use two-stage high/low fire instead of full modulation

Applicability and support

Model number
CBN315
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.

Lochinvar Copper-Fin Atmospheric CBN315 specifications
SpecificationValueNote
Input
Heating input, minimum157.5 MBHPer the I&O ratings table.
Heating input, maximum315 MBHPer the submittal sheet and the I&O ratings table.
Output
Gross output258 MBHGross output per the submittal sheet ratings table.
Net AHRI water rating224 MBHNet AHRI rating based on a piping and pickup allowance of 1.15, per the submittal and I&O ratings-table notes.
Efficiency
Efficiency (thermal)82 %82.0% thermal efficiency printed in the CBA-Sub-08 submittal and on the product page; no AFUE is published.
Venting and air
Vent size8"Per the submittal and I&O ratings tables.
VentingConventional negative draft (Category I) with built-in draft diverter; Type B double-wall ventThe I&O describes a conventional negative-draft system where the built-in draft diverter means no additional external draft hood is required; the product summary prints Category I, B-VENT material and -0.02 to -0.05 in. w.c. draft.
Physical and connections
Water content1.2 galPer the I&O ratings table.
Space-heating water connections2"2" NPT on 6-1/4" centers per the CBA-Sub-08 submittal.
Gas connection3/4"Per the submittal and I&O ratings tables.
Shipping weight245 lbShipping weight per the submittal sheet ratings table.
Dimension A29-1/2"As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal.
Dimension B32-1/4"As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal.
Dimension C21-1/2"As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal.
Dimension D16-1/4"As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal.
Operating limits and other
FiringTwo-stage (high/low fire)Two-stage intermittent electronic ignition and two-stage solid state temperature control per the CBA-Sub-08 standard features (firing code M9 standard).

Manuals

    Alerts documented for this model

    None documented yet.

    Services

    Frequently asked questions

    What are the CBN315's ratings?

    157.5 to 315 MBH input, 258 MBH gross output and a 224 MBH AHRI net water rating at 82.0% thermal efficiency, per the CBA-Sub-08 submittal and the I&O ratings table.

    How is the CBN315 vented?

    Conventionally, as a Category I negative-draft appliance through an 8" Type B double-wall vent; the built-in draft diverter means no additional external draft hood is required.

    Questions about the Lochinvar Copper-Fin Atmospheric CBN315?

    Describe what the boiler is doing and get a straight answer about the next step.

    On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

    Sources and verification

    Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.