Skip to content
Boilers.caby ROMA Heating & Cooling

Lochinvar · Copper-Fin (CBN/CHN)

Lochinvar Copper-Fin II CHN0502

The Copper-Fin II CHN0502 covers 250 to 500 MBH input with 425 MBH gross output and a 370 MBH AHRI net rating at 85% thermal efficiency on a 6" vent.

CurrentSold in Canada

Key figures

Max input
500 MBH
Max CSA output
AFUE
Min input
250 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Lochinvar Copper-Fin II CHN0502 in practice

The CHN0502 is the second Copper-Fin II size: the CHX I&O ratings table lists 250 to 500 MBH input, 425 MBH gross output and a 370 MBH AHRI net water rating at 85% thermal efficiency, with 1.9 gallons of water content. The CHE-Sub-11 submittal prints a 414 lb shipping weight, 6" vent and 6" air inlet on 2" NPT water connections (6-1/2" centers) and a 1-1/4" gas connection.

It keeps the 31-1/2" A and 22-1/4" C cabinet dimensions of the CHN0402 while growing the B dimension to 45-1/2", and it carries the line's SMART SYSTEM control with 8-boiler cascade, proportional firing up to 4:1, Category I/IV venting options and ANSI Z21.13/CSA 4.9 certification. The submittal prints 85% thermal efficiency (AHRI certified) and a 10-year limited warranty with 1-year parts.

Best suited to

  • Commercial loads near 500 MBH on 2" water piping
  • Cascaded plants using the SMART SYSTEM sequencer
  • Projects that want a 6" vent and air inlet at 500 MBH

Applicability and support

Model number
CHN0502
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.

Lochinvar Copper-Fin II CHN0502 specifications
SpecificationValueNote
Input
Heating input, minimum250 MBHPer the I&O ratings table.
Heating input, maximum500 MBHPer the submittal sheet and the I&O ratings table.
Output
Gross output425 MBHGross output per the submittal sheet ratings table.
Net AHRI water rating370 MBHNet AHRI rating based on a piping and pickup allowance of 1.15, per the submittal and I&O ratings-table notes.
Efficiency
Efficiency (thermal)85 %85% thermal efficiency (AHRI certified) printed in the CHE-Sub-11 submittal and on the product page; no AFUE is published.
Venting and air
Vent size6"Per the submittal and I&O ratings tables.
Air inlet size6"Per the CHE-Sub-11 submittal ratings table.
VentingCategory I (Type B double-wall) or Category IV (AL29-4C stainless steel); vertical or horizontalPer the CHE-Sub-11 standard features and the CHX I&O venting section; DirectAire and powered sidewall options are listed in the submittal.
Physical and connections
Water content1.9 galPer the I&O ratings table.
Space-heating water connections2"2" NPT on 6-1/2" centers per the CHE-Sub-11 submittal.
Gas connection1-1/4"Per the submittal and I&O ratings tables.
Shipping weight414 lbShipping weight per the submittal sheet ratings table.
Dimension A31-1/2"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension B45-1/2"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension C22-1/4"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension D12-1/2"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension E7"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension F7"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension G29"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension H6-1/2"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Operating limits and other
FiringProportional, up to 4:1 turndownProportional firing up to 4:1 turndown per the CHE-Sub-11 standard features; the CHX I&O ratings table prints minimum inputs of 250/360/630 MBH by size.

Manuals

    Alerts documented for this model

    None documented yet.

    Services

    Frequently asked questions

    What are the CHN0502's ratings?

    250 to 500 MBH input, 425 MBH gross output and a 370 MBH AHRI net water rating at 85% thermal efficiency, per the CHE-Sub-11 submittal and the CHX I&O ratings table.

    What vent and air sizes does the CHN0502 use?

    6" vent and 6" air inlet per the CHE-Sub-11 submittal, with Category I Type B or Category IV AL29-4C stainless steel vent materials.

    Questions about the Lochinvar Copper-Fin II CHN0502?

    Describe what the boiler is doing and get a straight answer about the next step.

    On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

    Sources and verification

    Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

    CallEmailEstimate