Lochinvar · Copper-Fin (CBN/CHN)
Lochinvar Copper-Fin Atmospheric CBN399
The Copper-Fin Atmospheric CBN399 runs 199.5 to 399 MBH input with 328 MBH gross output and a 285 MBH AHRI net rating at 82.0% thermal efficiency, stepping up to a 10" vent and a 1" gas connection.
Key figures
- Max input
- 399 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 199.5 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Copper-Fin Atmospheric CBN399 in practice
The CBN399 is the third atmospheric Copper-Fin size: 199.5 to 399 MBH input, a 285 MBH AHRI net water rating and 1.3 gallons of water content at 82.0% thermal efficiency. The CBA-Sub-08 submittal prints 328 MBH gross output, a 10" vent and a 320 lb shipping weight; the current I&O Rev A ratings table and the older product summary print 327 MBH / 327,999 BTU/hr for the same output, and the model record carries the submittal figure with that difference noted.
The cabinet grows to a 44-1/2" B dimension while keeping the 29-1/2" A dimension of the smaller sizes, and the boiler continues on 2" NPT water connections and a 1" gas connection. Firing is two-stage high/low (M9 standard), venting is Category I Type B through the built-in draft diverter, and the submittal prints a 10-year limited heat-exchanger warranty.
Best suited to
- Loads just under 400 MBH on a Category I vent system
- Projects stepping up from a 360 MBH boiler but staying under a 10" vent
- Buildings that want two-stage firing and a gasketless copper finned-tube exchanger
Applicability and support
- Model number
- CBN399
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 199.5 MBH | Per the I&O ratings table. |
| Heating input, maximum | 399 MBH | Per the submittal sheet and the I&O ratings table. |
| Output | ||
| Gross output | 328 MBH | Gross output per the submittal sheet ratings table. |
| Net AHRI water rating | 285 MBH | Net AHRI rating based on a piping and pickup allowance of 1.15, per the submittal and I&O ratings-table notes. |
| Efficiency | ||
| Efficiency (thermal) | 82 % | 82.0% thermal efficiency printed in the CBA-Sub-08 submittal and on the product page; no AFUE is published. |
| Venting and air | ||
| Vent size | 10" | Per the submittal and I&O ratings tables. |
| Venting | Conventional negative draft (Category I) with built-in draft diverter; Type B double-wall vent | The I&O describes a conventional negative-draft system where the built-in draft diverter means no additional external draft hood is required; the product summary prints Category I, B-VENT material and -0.02 to -0.05 in. w.c. draft. |
| Physical and connections | ||
| Water content | 1.3 gal | Per the I&O ratings table. |
| Space-heating water connections | 2" | 2" NPT on 6-1/4" centers per the CBA-Sub-08 submittal. |
| Gas connection | 1" | Per the submittal and I&O ratings tables. |
| Shipping weight | 320 lb | Shipping weight per the submittal sheet ratings table. |
| Dimension A | 29-1/2" | As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal. |
| Dimension B | 44-1/2" | As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal. |
| Dimension C | 22" | As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal. |
| Dimension D | 22-1/4" | As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal. |
| Operating limits and other | ||
| Firing | Two-stage (high/low fire) | Two-stage intermittent electronic ignition and two-stage solid state temperature control per the CBA-Sub-08 standard features (firing code M9 standard). |
Manuals
Alerts documented for this model
None documented yet.
Frequently asked questions
What are the CBN399's ratings?
199.5 to 399 MBH input, 328 MBH gross output and a 285 MBH AHRI net water rating at 82.0% thermal efficiency per CBA-Sub-08; the I&O ratings table prints the output as 327 MBH.
Why do sources differ on the CBN399 output?
The CBA-Sub-08 submittal prints 328 MBH while I&O Rev A and the product summary print 327 MBH (327,999 BTU/hr). The model record uses the submittal value and notes the difference rather than averaging them.
Questions about the Lochinvar Copper-Fin Atmospheric CBN399?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Lochinvar Copper-Fin Atmospheric CBN315Same series
- Lochinvar Copper-Fin Atmospheric CBN360Same series
- Lochinvar Copper-Fin Atmospheric CBN500Same series
- Lochinvar Copper-Fin Fan Assisted CBN0497Same series
- Lochinvar Copper-Fin Fan Assisted CBN0647Same series
- Lochinvar Copper-Fin Fan Assisted CBN0747Same series
- Lochinvar Copper-Fin Fan Assisted CBN0987Same series
- Lochinvar Copper-Fin Fan Assisted CBN1257Same series
- Lochinvar Copper-Fin Fan Assisted CBN1437Same series
- Lochinvar Copper-Fin Fan Assisted CBN1797Same series
- Lochinvar Copper-Fin Fan Assisted CBN2067Same series
- Lochinvar Copper-Fin II CHN0402Same series
- Lochinvar Copper-Fin II CHN0502Same series
- Lochinvar Copper-Fin II CHN0652Same series
- Lochinvar Copper-Fin II CHN0752Same series
- Lochinvar Copper-Fin II CHN0992Same series
- Lochinvar Copper-Fin II CHN1262Same series
- Lochinvar Copper-Fin II CHN1442Same series
- Lochinvar Copper-Fin II CHN1802Same series
- Lochinvar Copper-Fin II CHN2072Same series
- Copper-Fin (CBN/CHN) series hub
- Buying guide
Sources and verification
- Lochinvar — Copper-fin Atmospheric Commercial Boiler (CBN360) model page · accessed September 9, 2026
- Copper-Fin Atmospheric Boilers (CB 315-500) Submittal Sheet, CBA-Sub-08 · CBA-Sub-08 · accessed September 9, 2026
- Copper-Fin Atmospheric Commercial Boilers I&O Manual, Rev A · Rev A · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.