Lochinvar Copper-Fin II CHN0652

The Copper-Fin II CHN0652 covers 250 to 650 MBH input with 553 MBH gross output and a 481 MBH AHRI net rating at 85% thermal efficiency, moving to an 8" vent and air inlet.

CurrentSold in Canada

Key figures

Max input
650 MBH
Max CSA output
AFUE
Min input
250 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Lochinvar Copper-Fin II CHN0652 in practice

The CHN0652 sits in the middle of the four smaller Copper-Fin II sizes: 250 to 650 MBH input, 553 MBH gross output and a 481 MBH AHRI net water rating at 85% thermal efficiency, with 2.0 gallons of water content. The CHE-Sub-11 submittal prints a 500 lb shipping weight and 8" vent and air-inlet sizes, still on 2" NPT water (6-1/2" centers) and a 1-1/4" gas connection.

The cabinet grows to a 56-3/4" B dimension on the 31-1/2" A / 22-1/4" C platform, and the E and F dimensions step to 8-1/2" and 8-1/4". It carries the SMART SYSTEM control with built-in 8-boiler cascade, proportional firing up to 4:1, BMS integration, Category I/IV venting options and the line's 85% AHRI-certified thermal efficiency, 10-year limited warranty and 1-year parts coverage.

Best suited to

  • Commercial loads between 500 and 650 MBH
  • Plants stepping from a 6" to an 8" vent within the same cabinet family
  • Cascaded systems that need proportional firing at part load

Applicability and support

Model number
CHN0652
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.

Lochinvar Copper-Fin II CHN0652 specifications
SpecificationValueNote
Input
Heating input, minimum250 MBHPer the I&O ratings table.
Heating input, maximum650 MBHPer the submittal sheet and the I&O ratings table.
Output
Gross output553 MBHGross output per the submittal sheet ratings table.
Net AHRI water rating481 MBHNet AHRI rating based on a piping and pickup allowance of 1.15, per the submittal and I&O ratings-table notes.
Efficiency
Efficiency (thermal)85 %85% thermal efficiency (AHRI certified) printed in the CHE-Sub-11 submittal and on the product page; no AFUE is published.
Venting and air
Vent size8"Per the submittal and I&O ratings tables.
Air inlet size8"Per the CHE-Sub-11 submittal ratings table.
VentingCategory I (Type B double-wall) or Category IV (AL29-4C stainless steel); vertical or horizontalPer the CHE-Sub-11 standard features and the CHX I&O venting section; DirectAire and powered sidewall options are listed in the submittal.
Physical and connections
Water content2 galPer the I&O ratings table.
Space-heating water connections2"2" NPT on 6-1/2" centers per the CHE-Sub-11 submittal.
Gas connection1-1/4"Per the submittal and I&O ratings tables.
Shipping weight500 lbShipping weight per the submittal sheet ratings table.
Dimension A31-1/2"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension B56-3/4"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension C22-1/4"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension D12-1/2"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension E8-1/2"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension F8-1/4"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension G29"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Dimension H6-1/2"As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal.
Operating limits and other
FiringProportional, up to 4:1 turndownProportional firing up to 4:1 turndown per the CHE-Sub-11 standard features; the CHX I&O ratings table prints minimum inputs of 250/360/630 MBH by size.

Manuals

    Alerts documented for this model

    None documented yet.

    Services

    Frequently asked questions

    What are the CHN0652's ratings?

    250 to 650 MBH input, 553 MBH gross output and a 481 MBH AHRI net water rating at 85% thermal efficiency, per the CHE-Sub-11 submittal and the CHX I&O ratings table.

    Is the CHN0652 listed on Lochinvar's product page?

    The Copper-fin II product page's model selector lists CHN0402, CHN0502, CHN0752, CHN0992, CHN1262, CHN1442, CHN1802 and CHN2072; the CHN0652 is printed in the CHE-Sub-11 submittal, the current CHX I&O ratings table and the CH 652 plan-view drawing list, which are the sources for this record.

    Questions about the Lochinvar Copper-Fin II CHN0652?

    Describe what the boiler is doing and get a straight answer about the next step.

    On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

    Sources and verification

    Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

    CallEmailEstimate