Skip to content
Boilers.caby ROMA Heating & Cooling

Lochinvar · Copper-Fin (CBN/CHN)

Lochinvar Copper-Fin Atmospheric CBN500

The Copper-Fin Atmospheric CBN500 tops the atmospheric line at 250 to 500 MBH input with 410 MBH gross output and a 357 MBH AHRI net rating at 82.0% thermal efficiency.

CurrentSold in Canada

Key figures

Max input
500 MBH
Max CSA output
—
AFUE
—
Min input
250 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Lochinvar Copper-Fin Atmospheric CBN500 in practice

The CBN500 is the largest of the four printed atmospheric Copper-Fin sizes: the I&O ratings table lists 250 to 500 MBH input, 410 MBH gross output and a 357 MBH AHRI net water rating at 82.0% thermal efficiency, with 1.4 gallons of water content. The CBA-Sub-08 submittal prints a 345 lb shipping weight and the same 10" vent as the CBN399, on a 1" gas connection and 2" NPT water connections.

The cabinet uses a taller 34-1/2" A dimension and a 52-1/2" B dimension. Like the rest of the atmospheric line it is a Category I negative-draft boiler with a built-in draft diverter, two-stage high/low firing through a two-stage solid state control (M9 standard), and the gasketless ASME copper finned-tube heat exchanger at 160 psi. The submittal prints a 10-year limited heat-exchanger warranty.

Best suited to

  • Commercial loads at the top of the atmospheric range, near 500 MBH
  • Plants replacing an existing 500 MBH atmospheric boiler on Type B vent
  • Projects that need the largest draft-diverter Copper-Fin without moving to fan-assisted venting

Applicability and support

Model number
CBN500
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.

Lochinvar Copper-Fin Atmospheric CBN500 specifications
SpecificationValueNote
Input
Heating input, minimum250 MBHPer the I&O ratings table.
Heating input, maximum500 MBHPer the submittal sheet and the I&O ratings table.
Output
Gross output410 MBHGross output per the submittal sheet ratings table.
Net AHRI water rating357 MBHNet AHRI rating based on a piping and pickup allowance of 1.15, per the submittal and I&O ratings-table notes.
Efficiency
Efficiency (thermal)82 %82.0% thermal efficiency printed in the CBA-Sub-08 submittal and on the product page; no AFUE is published.
Venting and air
Vent size10"Per the submittal and I&O ratings tables.
VentingConventional negative draft (Category I) with built-in draft diverter; Type B double-wall ventThe I&O describes a conventional negative-draft system where the built-in draft diverter means no additional external draft hood is required; the product summary prints Category I, B-VENT material and -0.02 to -0.05 in. w.c. draft.
Physical and connections
Water content1.4 galPer the I&O ratings table.
Space-heating water connections2"2" NPT on 6-1/4" centers per the CBA-Sub-08 submittal.
Gas connection1"Per the submittal and I&O ratings tables.
Shipping weight345 lbShipping weight per the submittal sheet ratings table.
Dimension A34-1/2"As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal.
Dimension B52-1/2"As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal.
Dimension C22"As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal.
Dimension D26-1/4"As labeled on the CBA-Sub-08 dimension drawing; dimensions are approximate per the submittal.
Operating limits and other
FiringTwo-stage (high/low fire)Two-stage intermittent electronic ignition and two-stage solid state temperature control per the CBA-Sub-08 standard features (firing code M9 standard).

Manuals

    Alerts documented for this model

    None documented yet.

    Services

    Frequently asked questions

    What are the CBN500's ratings?

    250 to 500 MBH input, 410 MBH gross output and a 357 MBH AHRI net water rating at 82.0% thermal efficiency, per the CBA-Sub-08 submittal and the I&O ratings table.

    Is the CBN500 listed on Lochinvar's product page?

    The atmospheric product page's model selector lists CBN315, CBN360 and CBN399; the CBN500 is printed in the CBA-Sub-08 submittal, the current I&O ratings table and the plan-view drawing list, which are the sources for this record.

    Questions about the Lochinvar Copper-Fin Atmospheric CBN500?

    Describe what the boiler is doing and get a straight answer about the next step.

    On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

    Sources and verification

    Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

    CallEmailEstimate