Lochinvar · Copper-Fin (CBN/CHN)
Lochinvar Copper-Fin Fan Assisted CBN0987
The Copper-Fin Fan Assisted CBN0987 moves into the larger cabinet: 360 to 985 MBH input with 827 MBH gross output and a 719 MBH AHRI net rating at 84% thermal efficiency, on 2-1/2" water and 2" gas connections.
Key figures
- Max input
- 985 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 360 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Copper-Fin Fan Assisted CBN0987 in practice
The CBN0987 is the first fan-assisted size in the larger cabinet and the first on 2-1/2" NPT water connections (11-1/4" centers) and a 2" gas connection. The I&O ratings table lists 360 to 985 MBH input, 827 MBH gross output and a 719 MBH AHRI net water rating at 84% thermal efficiency, with 3.3 gallons of water content; the CB-Sub-14 submittal prints an 845 lb shipping weight and a 10" vent.
The cabinet dimensions change with the platform: a 36" A dimension, 48-1/4" B, 33-1/2" C and 15-3/4" D. The line's fan-assisted Category I design, sealed combustion chamber, hot surface ignition and two-stage electronic temperature control continue, and the total fan/control amp draw rises to 8.0 A. The submittal prints a 10-year limited heat-exchanger warranty.
Best suited to
- Loads approaching 1,000 MBH on a 10" vent
- Plants stepping up to 2-1/2" water and 2" gas connections
- Replacement projects that need the larger fan-assisted cabinet
Applicability and support
- Model number
- CBN0987
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 360 MBH | Per the I&O ratings table. |
| Heating input, maximum | 985 MBH | Per the submittal sheet and the I&O ratings table. |
| Output | ||
| Gross output | 827 MBH | Gross output per the submittal sheet ratings table. |
| Net AHRI water rating | 719 MBH | Net AHRI rating based on a piping and pickup allowance of 1.15, per the submittal and I&O ratings-table notes. |
| Efficiency | ||
| Efficiency (thermal) | 84 % | 84% thermal efficiency printed in the CB-Sub-14 submittal and on the product page; no AFUE is published. |
| Venting and air | ||
| Vent size | 10" | Per the submittal and I&O ratings tables. |
| Venting | Fan-assisted Category I; conventional negative draft or outdoor installation venting | The CBX I&O calls it a "fan-assisted Category 1 unit" with two venting options (conventional negative-draft vertical or outdoor installation); the sealed combustion chamber and combustion air filter are standard. |
| Physical and connections | ||
| Water content | 3.3 gal | Per the I&O ratings table. |
| Space-heating water connections | 2-1/2" | 2-1/2" NPT on 11-1/4" centers per the CB-Sub-14 submittal. |
| Gas connection | 2" | Per the submittal and I&O ratings tables. |
| Shipping weight | 845 lb | Shipping weight per the submittal sheet ratings table. |
| Dimension A | 36" | As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal. |
| Dimension B | 48-1/4" | As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal. |
| Dimension C | 33-1/2" | As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal. |
| Dimension D | 15-3/4" | As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal. |
| Dimension E | 8-1/2" | As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal. |
| Dimension F | 8-1/2" | As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal. |
| Dimension G | 33-3/4" | As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal. |
| Operating limits and other | ||
| Firing | Two-stage (high/low fire) | Two-stage electronic temperature control with hot surface ignition per the CB-Sub-14 standard features (M9 hot surface ignition with electronic supervision standard). |
Manuals
Alerts documented for this model
None documented yet.
Frequently asked questions
What are the CBN0987's ratings?
360 to 985 MBH input, 827 MBH gross output and a 719 MBH AHRI net water rating at 84% thermal efficiency, per the CB-Sub-14 submittal and the I&O ratings table.
When does the fan-assisted line change connections?
At the CBN0987: sizes 0497-0747 use 2" NPT water and 1-1/4" gas, while 0987-2067 use 2-1/2" NPT water on 11-1/4" centers and 2" gas, per the CB-Sub-14 submittal.
Questions about the Lochinvar Copper-Fin Fan Assisted CBN0987?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Lochinvar Copper-Fin Atmospheric CBN315Same series
- Lochinvar Copper-Fin Atmospheric CBN360Same series
- Lochinvar Copper-Fin Atmospheric CBN399Same series
- Lochinvar Copper-Fin Atmospheric CBN500Same series
- Lochinvar Copper-Fin Fan Assisted CBN0497Same series
- Lochinvar Copper-Fin Fan Assisted CBN0647Same series
- Lochinvar Copper-Fin Fan Assisted CBN0747Same series
- Lochinvar Copper-Fin Fan Assisted CBN1257Same series
- Lochinvar Copper-Fin Fan Assisted CBN1437Same series
- Lochinvar Copper-Fin Fan Assisted CBN1797Same series
- Lochinvar Copper-Fin Fan Assisted CBN2067Same series
- Lochinvar Copper-Fin II CHN0402Same series
- Lochinvar Copper-Fin II CHN0502Same series
- Lochinvar Copper-Fin II CHN0652Same series
- Lochinvar Copper-Fin II CHN0752Same series
- Lochinvar Copper-Fin II CHN0992Same series
- Lochinvar Copper-Fin II CHN1262Same series
- Lochinvar Copper-Fin II CHN1442Same series
- Lochinvar Copper-Fin II CHN1802Same series
- Lochinvar Copper-Fin II CHN2072Same series
- Copper-Fin (CBN/CHN) series hub
- Buying guide
Sources and verification
- Lochinvar — Copper-fin Commercial Gas Boiler (CBN0497) model page · accessed September 9, 2026
- Copper-Fin Gas-Fired Boilers (CB 0497-2067) Submittal Sheet, CB-Sub-14 · CB-Sub-14 · accessed September 9, 2026
- Copper-Fin Commercial Gas Boiler (CB Models only) I&O Manual, Rev A · Rev A · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.