Lochinvar Copper-Fin Fan Assisted CBN0647

The Copper-Fin Fan Assisted CBN0647 steps to 350 to 645 MBH input with 542 MBH gross output and a 471 MBH AHRI net rating at 84% thermal efficiency and an 8" vent.

CurrentSold in Canada

Key figures

Max input
645 MBH
Max CSA output
—
AFUE
—
Min input
350 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Lochinvar Copper-Fin Fan Assisted CBN0647 in practice

The CBN0647 is the second fan-assisted Copper-Fin size: the I&O ratings table lists 350 to 645 MBH input, 542 MBH gross output and a 471 MBH AHRI net water rating at 84% thermal efficiency, with 2.0 gallons of water content. The CB-Sub-14 submittal prints a 510 lb shipping weight and an 8" vent, with the same 1-1/4" gas connection and 2" NPT water connections on 6-1/2" centers as the CBN0497.

It shares the line's fan-assisted Category I design — sealed combustion chamber, hot surface ignition, two-stage electronic temperature control and a combustion air filter — and the cabinet grows to a 56-3/4" B dimension while keeping the 31-1/2" A dimension. The submittal lists a 10-year limited heat-exchanger warranty, and the fan/control amp draw for this size is 7.2 A total.

Best suited to

  • Mid-range commercial loads between 500 and 645 MBH
  • Plants that want an 8" vent rather than the 10"-14" sizes above it
  • Replacement work where the 56-3/4" cabinet width fits the mechanical room

Applicability and support

Model number
CBN0647
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.

Lochinvar Copper-Fin Fan Assisted CBN0647 specifications
SpecificationValueNote
Input
Heating input, minimum350 MBHPer the I&O ratings table.
Heating input, maximum645 MBHPer the submittal sheet and the I&O ratings table.
Output
Gross output542 MBHGross output per the submittal sheet ratings table.
Net AHRI water rating471 MBHNet AHRI rating based on a piping and pickup allowance of 1.15, per the submittal and I&O ratings-table notes.
Efficiency
Efficiency (thermal)84 %84% thermal efficiency printed in the CB-Sub-14 submittal and on the product page; no AFUE is published.
Venting and air
Vent size8"Per the submittal and I&O ratings tables.
VentingFan-assisted Category I; conventional negative draft or outdoor installation ventingThe CBX I&O calls it a "fan-assisted Category 1 unit" with two venting options (conventional negative-draft vertical or outdoor installation); the sealed combustion chamber and combustion air filter are standard.
Physical and connections
Water content2 galPer the I&O ratings table.
Space-heating water connections2"2" NPT on 6-1/2" centers per the CB-Sub-14 submittal.
Gas connection1-1/4"Per the submittal and I&O ratings tables.
Shipping weight510 lbShipping weight per the submittal sheet ratings table.
Dimension A31-1/2"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Dimension B56-3/4"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Dimension C22-1/4"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Dimension D12-1/2"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Dimension E9-1/2"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Dimension F28-1/2"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Dimension G29-1/2"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Operating limits and other
FiringTwo-stage (high/low fire)Two-stage electronic temperature control with hot surface ignition per the CB-Sub-14 standard features (M9 hot surface ignition with electronic supervision standard).

Manuals

    Alerts documented for this model

    None documented yet.

    Services

    Frequently asked questions

    What are the CBN0647's ratings?

    350 to 645 MBH input, 542 MBH gross output and a 471 MBH AHRI net water rating at 84% thermal efficiency, per the CB-Sub-14 submittal and the I&O ratings table.

    What vent size does the CBN0647 use?

    8" per the submittal and I&O ratings tables, with the line's conventional negative-draft or outdoor installation venting options.

    Questions about the Lochinvar Copper-Fin Fan Assisted CBN0647?

    Describe what the boiler is doing and get a straight answer about the next step.

    On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

    Sources and verification

    Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

    CallEmailEstimate