Lochinvar · Copper-Fin (CBN/CHN)
Lochinvar Copper-Fin II CHN0992
The Copper-Fin II CHN0992 moves to the larger cabinet and 2-1/2" water connections: 360 to 990 MBH input with 842 MBH gross output and a 732 MBH AHRI net rating at 85% thermal efficiency.
Key figures
- Max input
- 990 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 360 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Copper-Fin II CHN0992 in practice
The CHN0992 is the first Copper-Fin II size in the larger cabinet and the first on 2-1/2" NPT water connections (11-1/4" centers) and a 2" gas connection. The CHX I&O ratings table lists 360 to 990 MBH input, 842 MBH gross output and a 732 MBH AHRI net water rating at 85% thermal efficiency, with 3.3 gallons of water content; the CHE-Sub-11 submittal prints a 773 lb shipping weight with 10" vent and air-inlet sizes.
The cabinet changes to a 36" A dimension, 48-1/4" B, 33-1/2" C and 15-3/4" D, with an 8-3/4" H dimension. The SMART SYSTEM control with 8-boiler cascade, proportional firing up to 4:1, BMS integration and Category I/IV venting continue, and the submittal prints 85% AHRI-certified thermal efficiency with a 10-year limited warranty and 1-year parts.
Best suited to
- Loads approaching 1,000 MBH with proportional firing
- Plants stepping up to 2-1/2" water and 2" gas connections
- Cascaded Copper-Fin II systems in the larger cabinet
Applicability and support
- Model number
- CHN0992
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 360 MBH | Per the I&O ratings table. |
| Heating input, maximum | 990 MBH | Per the submittal sheet and the I&O ratings table. |
| Output | ||
| Gross output | 842 MBH | Gross output per the submittal sheet ratings table. |
| Net AHRI water rating | 732 MBH | Net AHRI rating based on a piping and pickup allowance of 1.15, per the submittal and I&O ratings-table notes. |
| Efficiency | ||
| Efficiency (thermal) | 85 % | 85% thermal efficiency (AHRI certified) printed in the CHE-Sub-11 submittal and on the product page; no AFUE is published. |
| Venting and air | ||
| Vent size | 10" | Per the submittal and I&O ratings tables. |
| Air inlet size | 10" | Per the CHE-Sub-11 submittal ratings table. |
| Venting | Category I (Type B double-wall) or Category IV (AL29-4C stainless steel); vertical or horizontal | Per the CHE-Sub-11 standard features and the CHX I&O venting section; DirectAire and powered sidewall options are listed in the submittal. |
| Physical and connections | ||
| Water content | 3.3 gal | Per the I&O ratings table. |
| Space-heating water connections | 2-1/2" | 2-1/2" NPT on 11-1/4" centers per the CHE-Sub-11 submittal. |
| Gas connection | 2" | Per the submittal and I&O ratings tables. |
| Shipping weight | 773 lb | Shipping weight per the submittal sheet ratings table. |
| Dimension A | 36" | As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal. |
| Dimension B | 48-1/4" | As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal. |
| Dimension C | 33-1/2" | As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal. |
| Dimension D | 15-3/4" | As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal. |
| Dimension E | 8-1/2" | As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal. |
| Dimension F | 8-1/2" | As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal. |
| Dimension G | 33-3/4" | As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal. |
| Dimension H | 8-3/4" | As labeled on the CHE-Sub-11 dimension drawing; dimensions are approximate per the submittal. |
| Operating limits and other | ||
| Firing | Proportional, up to 4:1 turndown | Proportional firing up to 4:1 turndown per the CHE-Sub-11 standard features; the CHX I&O ratings table prints minimum inputs of 250/360/630 MBH by size. |
Manuals
Alerts documented for this model
None documented yet.
Frequently asked questions
What are the CHN0992's ratings?
360 to 990 MBH input, 842 MBH gross output and a 732 MBH AHRI net water rating at 85% thermal efficiency, per the CHE-Sub-11 submittal and the CHX I&O ratings table.
When does the Copper-Fin II line change connections?
At the CHN0992: sizes 0402-0752 use 2" NPT water and 1-1/4" gas, while 0992-2072 use 2-1/2" NPT water on 11-1/4" centers and 2" gas, per the CHE-Sub-11 submittal.
Questions about the Lochinvar Copper-Fin II CHN0992?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Lochinvar Copper-Fin Atmospheric CBN315Same series
- Lochinvar Copper-Fin Atmospheric CBN360Same series
- Lochinvar Copper-Fin Atmospheric CBN399Same series
- Lochinvar Copper-Fin Atmospheric CBN500Same series
- Lochinvar Copper-Fin Fan Assisted CBN0497Same series
- Lochinvar Copper-Fin Fan Assisted CBN0647Same series
- Lochinvar Copper-Fin Fan Assisted CBN0747Same series
- Lochinvar Copper-Fin Fan Assisted CBN0987Same series
- Lochinvar Copper-Fin Fan Assisted CBN1257Same series
- Lochinvar Copper-Fin Fan Assisted CBN1437Same series
- Lochinvar Copper-Fin Fan Assisted CBN1797Same series
- Lochinvar Copper-Fin Fan Assisted CBN2067Same series
- Lochinvar Copper-Fin II CHN0402Same series
- Lochinvar Copper-Fin II CHN0502Same series
- Lochinvar Copper-Fin II CHN0652Same series
- Lochinvar Copper-Fin II CHN0752Same series
- Lochinvar Copper-Fin II CHN1262Same series
- Lochinvar Copper-Fin II CHN1442Same series
- Lochinvar Copper-Fin II CHN1802Same series
- Lochinvar Copper-Fin II CHN2072Same series
- Copper-Fin (CBN/CHN) series hub
- Buying guide
Sources and verification
- Lochinvar — Copper-fin II Commercial Gas Boiler (CHN0402) model page · accessed September 9, 2026
- Copper-Fin II Commercial Gas Boilers (CH 402-2072) Submittal Sheet, CHE-Sub-11 · CHE-Sub-11 · accessed September 9, 2026
- Copper-Fin II Commercial Gas Boilers (CHX Models only) I&O Manual, Rev A · Rev A · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.