Skip to content
Boilers.caby ROMA Heating & Cooling

Lochinvar · Copper-Fin (CBN/CHN)

Lochinvar Copper-Fin Fan Assisted CBN2067

The Copper-Fin Fan Assisted CBN2067 tops the line at 990 to 2,065 MBH input with 1,735 MBH gross output and a 1,508 MBH AHRI net rating at 84% thermal efficiency.

CurrentSold in Canada

Key figures

Max input
2,065 MBH
Max CSA output
—
AFUE
—
Min input
990 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Lochinvar Copper-Fin Fan Assisted CBN2067 in practice

The CBN2067 is the largest fan-assisted Copper-Fin: the I&O ratings table lists 990 to 2,065 MBH input, 1,735 MBH gross output and a 1,508 MBH AHRI net water rating at 84% thermal efficiency, with 4.3 gallons of water content. The CB-Sub-14 submittal prints a 1,350 lb shipping weight and a 14" vent on 2-1/2" NPT water and a 2" gas connection, and the minimum input rises to 990 MBH.

The cabinet reaches a 92-1/2" B dimension on the 36" A / 33-1/2" C / 15-3/4" D platform. The line's fan-assisted Category I design, sealed combustion chamber, hot surface ignition and two-stage electronic temperature control continue, with an 8.4 A total fan/control draw and a 10-year limited heat-exchanger warranty printed in the submittal.

Best suited to

  • The largest fan-assisted loads, near 2.0 million BTU/hr input
  • Plants that need a 14" Category I vent and 2-1/2" water connections
  • Replacement projects at the top of the fan-assisted range

Applicability and support

Model number
CBN2067
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.

Lochinvar Copper-Fin Fan Assisted CBN2067 specifications
SpecificationValueNote
Input
Heating input, minimum990 MBHPer the I&O ratings table.
Heating input, maximum2,065 MBHPer the submittal sheet and the I&O ratings table.
Output
Gross output1,735 MBHGross output per the submittal sheet ratings table.
Net AHRI water rating1,508 MBHNet AHRI rating based on a piping and pickup allowance of 1.15, per the submittal and I&O ratings-table notes.
Efficiency
Efficiency (thermal)84 %84% thermal efficiency printed in the CB-Sub-14 submittal and on the product page; no AFUE is published.
Venting and air
Vent size14"Per the submittal and I&O ratings tables.
VentingFan-assisted Category I; conventional negative draft or outdoor installation ventingThe CBX I&O calls it a "fan-assisted Category 1 unit" with two venting options (conventional negative-draft vertical or outdoor installation); the sealed combustion chamber and combustion air filter are standard.
Physical and connections
Water content4.3 galPer the I&O ratings table.
Space-heating water connections2-1/2"2-1/2" NPT on 11-1/4" centers per the CB-Sub-14 submittal.
Gas connection2"Per the submittal and I&O ratings tables.
Shipping weight1,350 lbShipping weight per the submittal sheet ratings table.
Dimension A36"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Dimension B92-1/2"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Dimension C33-1/2"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Dimension D15-3/4"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Dimension E11"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Dimension F11"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Dimension G33-3/4"As labeled on the CB-Sub-14 dimension drawing; dimensions are approximate per the submittal.
Operating limits and other
FiringTwo-stage (high/low fire)Two-stage electronic temperature control with hot surface ignition per the CB-Sub-14 standard features (M9 hot surface ignition with electronic supervision standard).

Manuals

    Alerts documented for this model

    None documented yet.

    Services

    Frequently asked questions

    What are the CBN2067's ratings?

    990 to 2,065 MBH input, 1,735 MBH gross output and a 1,508 MBH AHRI net water rating at 84% thermal efficiency, per the CB-Sub-14 submittal and the I&O ratings table.

    How does the CBN2067 compare with the Copper-Fin II CHN2072?

    Both reach about 2.07 million BTU/hr input, but the fan-assisted CBN2067 is rated 84% thermal efficiency with two-stage firing, while the CHN2072 is rated 85% with proportional firing up to 4:1 and the SMART SYSTEM control.

    Questions about the Lochinvar Copper-Fin Fan Assisted CBN2067?

    Describe what the boiler is doing and get a straight answer about the next step.

    On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

    Sources and verification

    Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

    CallEmailEstimate