Lochinvar Crest Flame Fail Running — Unit Was Running and Lost the Flame Signal
Flame Fail Running
Unit was running and lost the flame signal. The unit was running and lost the flame signal, so inspect the flame rods and associated wiring, check for proper electrical grounding, check the incoming gas supply pressure (natural gas 4 - 14 inches w.c., LP 8 - 14 inches w.c.), verify the vent and air intake pipes are installed correctly and unobstructed, inspect the flame sensor and burner, check combustion, and check or replace the filter. The table classifies it as Lockout (manual reset).
If you smell gas
- Stop what you are doing. Do not use phones, switches, matches or anything that can spark inside.
- Go outside and leave the door open behind you.
- Call the FortisBC 24-hour emergency line at 1-800-663-9911 or dial 911.
Only after that, call ROMA about the boiler. Official guidance: FortisBC gas leaks and odour.
Applies to
This flame fault code is displayed by the Crest control (text faults) on Crest with Hellcat models (FCB1000 through FCB6000), as documented in Crest with Hellcat (FCB) Service Manual, 100343237 Rev D — Table 3G fault codes (100343237 Rev D). Codes can differ between controller generations, so always check the manual that matches your unit.
- Lochinvar Crest (FB / Hellcat FCB)
- Lochinvar Crest FBN0751
- Lochinvar Crest FBN1001
- Lochinvar Crest FBN1251
- Lochinvar Crest FBN1501
- Lochinvar Crest FBN1751
- Lochinvar Crest FBN2001
- Lochinvar Crest FBN2501
- Lochinvar Crest FBN3001
- Lochinvar Crest FBN3501
- Lochinvar Crest FBN4001
- Lochinvar Crest FBN5001
- Lochinvar Crest FBN6001
- Lochinvar Crest FCB1000
- Lochinvar Crest FCB1500
- Lochinvar Crest FCB2000
- Lochinvar Crest FCB2500
- Lochinvar Crest FCB3000
- Lochinvar Crest FCB4000
- Lochinvar Crest FCB5000
- Lochinvar Crest FCB6000
Controller: Crest control (text faults). Source manual: 100343237 Rev D (2025-07).
Why a code is not a diagnosis
A flame code during operation can come from a blocked condensate or vent path, gas pressure moving out of range, wind at the terminal, or a fouled flame sensor. Only on-site testing identifies the cause.
Safe things to observe
- If you smell gas, stop, go outside and call your gas utility's emergency line or 911 before anything else.
- Note the exact code and what the appliance was doing when it appeared.
- Check whether other gas appliances in the building are working.
Do not
- Do not keep resetting while the cause is unknown.
- Do not touch gas, ignition or combustion components.
How professional service helps
- A technician checks condensate, venting, gas pressure at low and high fire, and combustion readings.
- Combustion and safety devices are verified with an analyser and the manufacturer's procedure after any repair.
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Parts and service
Parts commonly involved
These parts appear in the documented text for this alert. A code reports a condition, not a failed part — a technician confirms the cause by testing before anything is replaced.
Flame sensor (flame rod)
The flame sensor is the small rod that proves a gas boiler's burner is actually lit before the control will keep the gas valve open.
What a technician checks →Burner assembly
The burner assembly is where gas and air meet and burn inside a boiler, and its condition decides whether combustion is clean or makes carbon…
What a technician checks →Boiler venting (flue and air intake)
A condensing boiler vents cool, wet flue gases through dedicated plastic pipe that must meet ULC S636 in Canada and the boiler manufacturer's own…
What a technician checks →
Service for this alert
- Gas Boiler Repair
Licensed gas technicians from ROMA Heating & Cooling diagnose and repair residential and light-commercial gas boilers across…
- Emergency Boiler Repair
Priority gas boiler repair for homes and buildings in Greater Vancouver with no heat, no hot water, a locked-out boiler or a leak.
Every boiler part explained — what it does, how it fails and what a technician checks.
Documented for Lochinvar Crest (FB / Hellcat FCB).
Frequently asked questions
Does this code mean I have a gas leak?
Not by itself. If you smell gas, stop, leave the building and call your gas utility's emergency line or 911 from outside before anything else. Otherwise the code points to a fault a technician confirms on site.
Can I clear this code myself?
Clearing a code without fixing its cause usually just brings it back. Note the code, check the safe items on this page, then call a licensed technician. If your appliance manual describes a user reset for this exact code and it stays away, no call may be needed.
Boiler locked out? Call with the alert text ready.
The brand, model and this alert are passed along when you request service online, so the technician arrives prepared.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- Crest with Hellcat (FCB) Service Manual, 100343237 Rev D — Table 3G fault codes · 100343237 Rev D · accessed September 7, 2026
Facts checked September 7, 2026. Last updated September 7, 2026. Technical reviewer: not yet assigned.