Lochinvar · Crest (FB / Hellcat FCB)
Lochinvar Crest FCB6000
The Crest with Hellcat FCB6000 tops the FCB range at 300 to 6000 MBH input with 5766 MBH gross output and a 5014 MBH AHRI net rating, on 6" pipe with a 3" gas inlet.
Key figures
- Max input
- 6,000 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 300 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Crest FCB6000 in practice
The FCB6000 is the largest Crest with Hellcat: the I&O ratings table lists 300 to 6000 MBH input with 5766 MBH gross output and a 5014 MBH AHRI net water rating, and it sits at the top of the FCB1000-6000 range the page copy rates at 20:1 turndown. Water content reaches 304 gallons and weight with water 6,900 lb, with the 6" pipe outlet and inlet continued from the 5000 and the gas inlet growing to 3".
Air and vent are both 14" per the ratings table. The Hellcat combustion system with RealTime O2 Trim, the full-color 10" capacitive touchscreen and common-vent capability in stainless steel, polypropylene, PVC or CPVC to 150 equivalent feet define the flagship, and Lochinvar's Hellcat page lists voltages to 480 for the FCB line.
Best suited to
- The largest central plants in the FCB range, near 6.0 million BTU/hr
- Projects with a 3" gas supply and 14" air/vent openings on Hellcat
- Plants wanting 20:1 turndown at the top of the Crest with Hellcat line
Applicability and support
- Model number
- FCB6000
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 300 MBH | Per the I&O ratings table. |
| Heating input, maximum | 6,000 MBH | Per the I&O ratings table. |
| Output | ||
| Gross output | 5,766 MBH | Per the I&O ratings table. |
| Net AHRI water rating | 5,014 MBH | Per the I&O ratings table. |
| Venting and air | ||
| Air size | 14" | Per the I&O ratings table. |
| Vent size | 14" | Per the I&O ratings table. |
| Venting | Category IV sealed combustion; room air/direct vent/common vent in stainless steel, polypropylene, PVC or CPVC | Up to 150 equivalent feet per the Crest with Hellcat product-page feature list. |
| Physical and connections | ||
| Water content | 304 gal | Per the I&O ratings table. |
| Pipe outlet connection | 6" | Per the I&O ratings table. |
| Pipe inlet connection | 6" | Per the I&O ratings table. |
| Gas connection | 3" | Per the I&O ratings table. |
| Weight with water | 6,900 lb | Per the I&O ratings table. |
Manuals
Alerts documented for this model
- Gas Pressure SW Open
- Low Water Cutoff Open
- Blocked Drain SW Open
- APS Open
- Anti-cycling
- Flame Failure
- Flame Fail Running
- Gas Valve / Relay Failure
- Auto Reset High Limit
- Manual Reset High Limit Open
- Fan Speed Low
- Fan Speed High
- Louver Proving Sw Open
- Flue Temp High
- Delta T High
- Outlet Temp High
- Parameter Programming Complete
- Sensor Open
- Sensor Shorted
- Flue Sensor Open
- Flue Sensor Shorted
- Too Many Resets - Try Later
- Internal Fault
- Flue Temp Shutdown
- Delta T Shutdown
- Outlet Temp Shutdown
- Writing/Programming EEProm Error
- CRC Parameter Error
- Wrong Error Code
- Flame Sense Out of Sequence 1
- Flame Sense Out of Sequence 2
- Flue Damper Switch Open
- IO Expander Out Error
- Failure ADC Controller
- Outlet Sensor Differential
- Flue Sensor Differential
Frequently asked questions
What are the FCB6000's ratings?
300 to 6000 MBH of input with 5766 MBH gross output and a 5014 MBH AHRI net water rating per the I&O ratings table.
What connections does the FCB6000 use?
6" pipe outlet and inlet, a 3" gas inlet and 14" air and vent sizes, with a 304-gallon water content and 6,900 lb weight with water per the ratings table.
Questions about the Lochinvar Crest FCB6000?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Lochinvar Crest FCB5000 vs FCB6000Comparison
- Lochinvar Crest FBN0751Same series
- Lochinvar Crest FBN1001Same series
- Lochinvar Crest FBN1251Same series
- Lochinvar Crest FBN1501Same series
- Lochinvar Crest FBN1751Same series
- Lochinvar Crest FBN2001Same series
- Lochinvar Crest FBN2501Same series
- Lochinvar Crest FBN3001Same series
- Lochinvar Crest FBN3501Same series
- Lochinvar Crest FBN4001Same series
- Lochinvar Crest FBN5001Same series
- Lochinvar Crest FBN6001Same series
- Lochinvar Crest FCB1000Same series
- Lochinvar Crest FCB1500Same series
- Lochinvar Crest FCB2000Same series
- Lochinvar Crest FCB2500Same series
- Lochinvar Crest FCB3000Same series
- Lochinvar Crest FCB4000Same series
- Lochinvar Crest FCB5000Same series
- Crest (FB / Hellcat FCB) series hub
- Buying guide
Sources and verification
- Lochinvar — Crest with Hellcat (FCB4000N) model page · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.