Lochinvar Crest FBN3001

The Crest FBN3001 fires 150 to 3000 MBH with 2883 MBH gross output and a 2507 MBH AHRI net rating at 20:1 turndown, stepping air and vent to 10" at a 3.0 million BTU/hr ceiling.

CurrentSold in Canada

Key figures

Max input
3,000 MBH
Max CSA output
AFUE
Min input
150 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Lochinvar Crest FBN3001 in practice

The FBN3001 lifts the Crest FB line to 3.0 million BTU/hr of input: the I&O ratings table lists 150 to 3000 MBH with 2883 MBH gross output and a 2507 MBH AHRI net water rating, at 20:1 turndown per the manual. Water content is 156 gallons and weight with water 3,900 lb, with the 4" pipe connections and 2" gas inlet carried over from the 2501.

Air and vent both step to 10" at this size per the ratings table. Venting is in stainless steel, polypropylene, PVC or CPVC to 100 equivalent feet per the page feature list, and the boiler runs the wave fire-tube platform with the SMART TOUCH control and CON·X·US from the Crest family page, which prints the 10-year heat exchanger warranty.

Best suited to

  • Commercial and institutional loads near 3.0 million BTU/hr
  • Plants planned around 10" air intake and 10" vent openings
  • Systems wanting 20:1 turndown at the 3001 size

Applicability and support

Model number
FBN3001
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.

Lochinvar Crest FBN3001 specifications
SpecificationValueNote
Input
Heating input, minimum150 MBHPer the I&O ratings table.
Heating input, maximum3,000 MBHPer the I&O ratings table.
Output
Gross output2,883 MBHPer the I&O ratings table.
Net AHRI water rating2,507 MBHPer the I&O ratings table.
Venting and air
Air size10"Per the I&O ratings table.
Vent size10"Per the I&O ratings table.
VentingCategory IV sealed combustion; stainless steel, polypropylene, PVC or CPVC ventingUp to 100 equivalent feet per the Crest product-page feature list.
Physical and connections
Water content156 galPer the I&O ratings table.
Pipe outlet connection4"Per the I&O ratings table.
Pipe inlet connection4"Per the I&O ratings table.
Gas connection2"Per the I&O ratings table.
Weight with water3,900 lbPer the I&O ratings table.

Frequently asked questions

What are the FBN3001's ratings?

150 to 3000 MBH of input with 2883 MBH gross output and a 2507 MBH AHRI net water rating per the I&O ratings table, at 20:1 turndown.

How does the FBN3001 differ from the FBN2501?

Maximum input rises from 2500 to 3000 MBH, air and vent both grow from 8"/9" to 10"/10", and weight with water rises from 3,600 to 3,900 lb; the pipe stays 4" and the gas inlet stays 2".

Questions about the Lochinvar Crest FBN3001?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate