Lochinvar · Crest (FB / Hellcat FCB)
Lochinvar Crest FCB5000
The Crest with Hellcat FCB5000 fires 250 to 4999 MBH with 4804 MBH gross output and a 4177 MBH AHRI net rating, stepping the Hellcat line to 6" pipe and 14" air and vent.
Key figures
- Max input
- 4,999 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 250 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Crest FCB5000 in practice
The FCB5000 is the first Hellcat size on 6" pipe: the I&O ratings table lists 250 to 4999 MBH input with 4804 MBH gross output and a 4177 MBH AHRI net water rating. It is among the FCB2500-6000 sizes the page copy rates at 20:1 turndown, and water content grows to 254 gallons with the gas inlet at 2-1/2" and air and vent both 14".
Weight with water is 5,900 lb per the ratings table. The Hellcat combustion system with RealTime O2 Trim and the 10" capacitive touchscreen control carry through, and venting is room air/direct vent or common vent in stainless steel, polypropylene, PVC or CPVC to 150 equivalent feet per the page feature list, with voltages to 480 available on the line.
Best suited to
- Central plants in the 4.0 to 5.0 million BTU/hr range on Hellcat
- Projects already planned around 6" boiler piping
- Designs with a 250 MBH minimum fire and 20:1 turndown
Applicability and support
- Model number
- FCB5000
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 250 MBH | Per the I&O ratings table. |
| Heating input, maximum | 4,999 MBH | Per the I&O ratings table. |
| Output | ||
| Gross output | 4,804 MBH | Per the I&O ratings table. |
| Net AHRI water rating | 4,177 MBH | Per the I&O ratings table. |
| Venting and air | ||
| Air size | 14" | Per the I&O ratings table. |
| Vent size | 14" | Per the I&O ratings table. |
| Venting | Category IV sealed combustion; room air/direct vent/common vent in stainless steel, polypropylene, PVC or CPVC | Up to 150 equivalent feet per the Crest with Hellcat product-page feature list. |
| Physical and connections | ||
| Water content | 254 gal | Per the I&O ratings table. |
| Pipe outlet connection | 6" | Per the I&O ratings table. |
| Pipe inlet connection | 6" | Per the I&O ratings table. |
| Gas connection | 2-1/2" | Per the I&O ratings table. |
| Weight with water | 5,900 lb | Per the I&O ratings table. |
Manuals
Alerts documented for this model
- Gas Pressure SW Open
- Low Water Cutoff Open
- Blocked Drain SW Open
- APS Open
- Anti-cycling
- Flame Failure
- Flame Fail Running
- Gas Valve / Relay Failure
- Auto Reset High Limit
- Manual Reset High Limit Open
- Fan Speed Low
- Fan Speed High
- Louver Proving Sw Open
- Flue Temp High
- Delta T High
- Outlet Temp High
- Parameter Programming Complete
- Sensor Open
- Sensor Shorted
- Flue Sensor Open
- Flue Sensor Shorted
- Too Many Resets - Try Later
- Internal Fault
- Flue Temp Shutdown
- Delta T Shutdown
- Outlet Temp Shutdown
- Writing/Programming EEProm Error
- CRC Parameter Error
- Wrong Error Code
- Flame Sense Out of Sequence 1
- Flame Sense Out of Sequence 2
- Flue Damper Switch Open
- IO Expander Out Error
- Failure ADC Controller
- Outlet Sensor Differential
- Flue Sensor Differential
Frequently asked questions
What are the FCB5000's ratings?
250 to 4999 MBH of input with 4804 MBH gross output and a 4177 MBH AHRI net water rating per the I&O ratings table.
What connections does the FCB5000 use?
6" pipe outlet and inlet, a 2-1/2" gas inlet and 14" air and vent sizes, with a 254-gallon water content and 5,900 lb weight with water per the ratings table.
Questions about the Lochinvar Crest FCB5000?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Lochinvar Crest FCB5000 vs FCB6000Comparison
- Lochinvar Crest FBN0751Same series
- Lochinvar Crest FBN1001Same series
- Lochinvar Crest FBN1251Same series
- Lochinvar Crest FBN1501Same series
- Lochinvar Crest FBN1751Same series
- Lochinvar Crest FBN2001Same series
- Lochinvar Crest FBN2501Same series
- Lochinvar Crest FBN3001Same series
- Lochinvar Crest FBN3501Same series
- Lochinvar Crest FBN4001Same series
- Lochinvar Crest FBN5001Same series
- Lochinvar Crest FBN6001Same series
- Lochinvar Crest FCB1000Same series
- Lochinvar Crest FCB1500Same series
- Lochinvar Crest FCB2000Same series
- Lochinvar Crest FCB2500Same series
- Lochinvar Crest FCB3000Same series
- Lochinvar Crest FCB4000Same series
- Lochinvar Crest FCB6000Same series
- Crest (FB / Hellcat FCB) series hub