Skip to content
Boilers.caby ROMA Heating & Cooling

Lochinvar · Crest (FB / Hellcat FCB)

Lochinvar Crest FCB2500

The Crest with Hellcat FCB2500 fires 125 to 2500 MBH with 2400 MBH gross output and a 2087 MBH AHRI net rating — the entry of the FCB sizes Lochinvar's page copy rates at 20:1 turndown.

CurrentSold in Canada

Key figures

Max input
2,500 MBH
Max CSA output
—
AFUE
—
Min input
125 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Lochinvar Crest FCB2500 in practice

The FCB2500 opens the upper half of the Crest with Hellcat range at 2.5 million BTU/hr: the I&O ratings table lists 125 to 2500 MBH input with 2400 MBH gross output and a 2087 MBH AHRI net water rating. Lochinvar's Hellcat page copy states 20:1 turndown for the FCB2500-6000 sizes, and the FCB4000N page's feature copy carries the same claim for the line.

Connections follow the FB2501 pattern — 4" pipe outlet and inlet, a 2" gas inlet and an 8" air size with a 9" vent — with water content at 157 gallons and weight with water at 3,600 lb per the ratings table. RealTime O2 Trim combustion, the 10" capacitive touchscreen and venting to 150 equivalent feet in stainless steel, polypropylene, PVC or CPVC complete the Hellcat package.

Best suited to

  • Central plants entering the 20:1-turndown band of the FCB line at 2.5 million BTU/hr
  • Projects stepping to a 2" gas connection with 4" boiler piping
  • Plants that want Hellcat combustion at the FCB2500's specific air/vent sizes

Applicability and support

Model number
FCB2500
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.

Lochinvar Crest FCB2500 specifications
SpecificationValueNote
Input
Heating input, minimum125 MBHPer the I&O ratings table.
Heating input, maximum2,500 MBHPer the I&O ratings table.
Output
Gross output2,400 MBHPer the I&O ratings table.
Net AHRI water rating2,087 MBHPer the I&O ratings table.
Venting and air
Air size8"Per the I&O ratings table.
Vent size9"Per the I&O ratings table.
VentingCategory IV sealed combustion; room air/direct vent/common vent in stainless steel, polypropylene, PVC or CPVCUp to 150 equivalent feet per the Crest with Hellcat product-page feature list.
Physical and connections
Water content157 galPer the I&O ratings table.
Pipe outlet connection4"Per the I&O ratings table.
Pipe inlet connection4"Per the I&O ratings table.
Gas connection2"Per the I&O ratings table.
Weight with water3,600 lbPer the I&O ratings table.

Frequently asked questions

What are the FCB2500's ratings?

125 to 2500 MBH of input with 2400 MBH gross output and a 2087 MBH AHRI net water rating per the I&O ratings table.

What turndown does Lochinvar claim for the FCB2500?

The Hellcat page copy states 20:1 turndown for the FCB2500-6000 sizes; the FCB4000N product page prints the 20:1 headline for the line.

Questions about the Lochinvar Crest FCB2500?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate