Lochinvar Crest FBN2501

The Crest FBN2501 fires 125 to 2500 MBH with 2400 MBH gross output and a 2087 MBH AHRI net rating at 20:1 turndown, stepping the gas inlet to 2" with a 9" vent.

CurrentSold in Canada

Key figures

Max input
2,500 MBH
Max CSA output
—
AFUE
—
Min input
125 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Lochinvar Crest FBN2501 in practice

The FBN2501 opens the upper half of the Crest FB line at 2.5 million BTU/hr: the I&O ratings table lists 125 to 2500 MBH input with 2400 MBH gross output and a 2087 MBH AHRI net water rating, at 20:1 turndown per the manual. Water content jumps to 157 gallons, weight with water to 3,600 lb, and the 4" pipe connections stay while the gas inlet grows to 2".

The ratings table prints an 8" air size with a 9" vent for the 2501, and the I&O adds that FB 2501 models using the 10" vent diameter option must use the appropriate increase adapters. Venting is in stainless steel, polypropylene, PVC or CPVC to 100 equivalent feet per the page feature list, on the wave fire-tube platform with the SMART TOUCH control.

Best suited to

  • Large commercial and institutional plants at 2.5 million BTU/hr
  • Projects stepping up to a 2" gas connection at the boiler
  • Designs that plan the 2501's specific 9" vent or the 10" adapter option

Applicability and support

Model number
FBN2501
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.

Lochinvar Crest FBN2501 specifications
SpecificationValueNote
Input
Heating input, minimum125 MBHPer the I&O ratings table.
Heating input, maximum2,500 MBHPer the I&O ratings table.
Output
Gross output2,400 MBHPer the I&O ratings table.
Net AHRI water rating2,087 MBHPer the I&O ratings table.
Venting and air
Air size8"Per the I&O ratings table.
Vent size9"Per the I&O ratings table.
VentingCategory IV sealed combustion; stainless steel, polypropylene, PVC or CPVC ventingUp to 100 equivalent feet per the Crest product-page feature list.
Physical and connections
Water content157 galPer the I&O ratings table.
Pipe outlet connection4"Per the I&O ratings table.
Pipe inlet connection4"Per the I&O ratings table.
Gas connection2"Per the I&O ratings table.
Weight with water3,600 lbPer the I&O ratings table.

Frequently asked questions

What are the FBN2501's ratings?

125 to 2500 MBH of input with 2400 MBH gross output and a 2087 MBH AHRI net water rating per the I&O ratings table, at 20:1 turndown.

What venting does the FBN2501 use?

The ratings table prints an 8" air size and 9" vent, and the I&O notes that 2501 models using the 10" vent diameter option need the appropriate increase adapters.

Questions about the Lochinvar Crest FBN2501?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.