Lochinvar · Crest (FB / Hellcat FCB)
Lochinvar Crest FBN2501
The Crest FBN2501 fires 125 to 2500 MBH with 2400 MBH gross output and a 2087 MBH AHRI net rating at 20:1 turndown, stepping the gas inlet to 2" with a 9" vent.
Key figures
- Max input
- 2,500 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 125 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Crest FBN2501 in practice
The FBN2501 opens the upper half of the Crest FB line at 2.5 million BTU/hr: the I&O ratings table lists 125 to 2500 MBH input with 2400 MBH gross output and a 2087 MBH AHRI net water rating, at 20:1 turndown per the manual. Water content jumps to 157 gallons, weight with water to 3,600 lb, and the 4" pipe connections stay while the gas inlet grows to 2".
The ratings table prints an 8" air size with a 9" vent for the 2501, and the I&O adds that FB 2501 models using the 10" vent diameter option must use the appropriate increase adapters. Venting is in stainless steel, polypropylene, PVC or CPVC to 100 equivalent feet per the page feature list, on the wave fire-tube platform with the SMART TOUCH control.
Best suited to
- Large commercial and institutional plants at 2.5 million BTU/hr
- Projects stepping up to a 2" gas connection at the boiler
- Designs that plan the 2501's specific 9" vent or the 10" adapter option
Applicability and support
- Model number
- FBN2501
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 125 MBH | Per the I&O ratings table. |
| Heating input, maximum | 2,500 MBH | Per the I&O ratings table. |
| Output | ||
| Gross output | 2,400 MBH | Per the I&O ratings table. |
| Net AHRI water rating | 2,087 MBH | Per the I&O ratings table. |
| Venting and air | ||
| Air size | 8" | Per the I&O ratings table. |
| Vent size | 9" | Per the I&O ratings table. |
| Venting | Category IV sealed combustion; stainless steel, polypropylene, PVC or CPVC venting | Up to 100 equivalent feet per the Crest product-page feature list. |
| Physical and connections | ||
| Water content | 157 gal | Per the I&O ratings table. |
| Pipe outlet connection | 4" | Per the I&O ratings table. |
| Pipe inlet connection | 4" | Per the I&O ratings table. |
| Gas connection | 2" | Per the I&O ratings table. |
| Weight with water | 3,600 lb | Per the I&O ratings table. |
Manuals
Alerts documented for this model
- Gas Pressure SW Open
- Low Water Cutoff Open
- Blocked Drain SW Open
- APS Open
- Anti-cycling
- Flame Failure
- Flame Fail Running
- Gas Valve / Relay Failure
- Auto Reset High Limit
- Manual Reset High Limit Open
- Fan Speed Low
- Fan Speed High
- Louver Proving Sw Open
- Flue Temp High
- Delta T High
- Outlet Temp High
- Parameter Programming Complete
- Sensor Open
- Sensor Shorted
- Flue Sensor Open
- Flue Sensor Shorted
- Too Many Resets - Try Later
- Internal Fault
- Flue Temp Shutdown
- Delta T Shutdown
- Outlet Temp Shutdown
- Writing/Programming EEProm Error
- CRC Parameter Error
- Wrong Error Code
- Flame Sense Out of Sequence 1
- Flame Sense Out of Sequence 2
- Flue Damper Switch Open
- IO Expander Out Error
- Failure ADC Controller
- Outlet Sensor Differential
- Flue Sensor Differential
Frequently asked questions
What are the FBN2501's ratings?
125 to 2500 MBH of input with 2400 MBH gross output and a 2087 MBH AHRI net water rating per the I&O ratings table, at 20:1 turndown.
What venting does the FBN2501 use?
The ratings table prints an 8" air size and 9" vent, and the I&O notes that 2501 models using the 10" vent diameter option need the appropriate increase adapters.
Questions about the Lochinvar Crest FBN2501?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Lochinvar Crest FBN2001 vs FBN2501Comparison
- Lochinvar Crest FBN2501 vs FBN3001Comparison
- Lochinvar Crest FBN0751Same series
- Lochinvar Crest FBN1001Same series
- Lochinvar Crest FBN1251Same series
- Lochinvar Crest FBN1501Same series
- Lochinvar Crest FBN1751Same series
- Lochinvar Crest FBN2001Same series
- Lochinvar Crest FBN3001Same series
- Lochinvar Crest FBN3501Same series
- Lochinvar Crest FBN4001Same series
- Lochinvar Crest FBN5001Same series
- Lochinvar Crest FBN6001Same series
- Lochinvar Crest FCB1000Same series
- Lochinvar Crest FCB1500Same series
- Lochinvar Crest FCB2000Same series
- Lochinvar Crest FCB2500Same series
- Lochinvar Crest FCB3000Same series
- Lochinvar Crest FCB4000Same series
- Lochinvar Crest FCB5000Same series
- Lochinvar Crest FCB6000Same series
- Crest (FB / Hellcat FCB) series hub
- Buying guide
Sources and verification
- Lochinvar — Crest Condensing Boiler (FBN1001) model page · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.