Lochinvar Crest FBN2001

The Crest FBN2001 fires 80 to 1999 MBH with 1923 MBH gross output and a 1699 MBH AHRI net rating at 25:1 turndown, closing the 25:1 band of the FB line.

CurrentSold in Canada

Key figures

Max input
1,999 MBH
Max CSA output
AFUE
Min input
80 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Lochinvar Crest FBN2001 in practice

The FBN2001 is the largest of the Crest sizes with 25:1 turndown: the I&O ratings table lists 80 to 1999 MBH input with 1923 MBH gross output and a 1699 MBH AHRI net water rating, and the manual assigns 25:1 turndown to the 1501-2001 models. Its 111-gallon water content and 2,570 lb weight-with-water sit at the top of the 4"-pipe family.

Connections match the 1501 and 1751: 4" pipe outlet and inlet, 1-1/2" gas inlet and 8" air and vent. Venting is in stainless steel, polypropylene, PVC or CPVC to 100 equivalent feet per the page feature list, and the boiler runs the wave fire-tube platform with the SMART TOUCH control and CON·X·US from the Crest family page.

Best suited to

  • Commercial loads approaching 2,000 MBH on a single boiler
  • Plants that want 25:1 turndown at the largest FB size that offers it
  • Projects with 4" piping and 8" air/vent already designed in

Applicability and support

Model number
FBN2001
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.

Lochinvar Crest FBN2001 specifications
SpecificationValueNote
Input
Heating input, minimum80 MBHPer the I&O ratings table.
Heating input, maximum1,999 MBHPer the I&O ratings table.
Output
Gross output1,923 MBHPer the I&O ratings table.
Net AHRI water rating1,699 MBHPer the I&O ratings table.
Venting and air
Air size8"Per the I&O ratings table.
Vent size8"Per the I&O ratings table.
VentingCategory IV sealed combustion; stainless steel, polypropylene, PVC or CPVC ventingUp to 100 equivalent feet per the Crest product-page feature list.
Physical and connections
Water content111 galPer the I&O ratings table.
Pipe outlet connection4"Per the I&O ratings table.
Pipe inlet connection4"Per the I&O ratings table.
Gas connection1-1/2"Per the I&O ratings table.
Weight with water2,570 lbPer the I&O ratings table.

Frequently asked questions

What are the FBN2001's ratings?

80 to 1999 MBH of input with 1923 MBH gross output and a 1699 MBH AHRI net water rating per the I&O ratings table, at 25:1 turndown.

Which Crest FB models share the FBN2001's connections?

The 1501, 1751 and 2001 all use 4" pipe outlet and inlet with a 1-1/2" gas inlet and 8" air and vent; they differ in capacity, water content and weight.

Questions about the Lochinvar Crest FBN2001?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate