Lochinvar · Crest (FB / Hellcat FCB)
Lochinvar Crest FBN0751
The Crest FBN0751 opens the Crest FB line at 50 to 750 MBH input with 722 MBH gross output and a 626 MBH AHRI net rating, on 3" pipe connections with 6" air and vent — 15:1 turndown.
Key figures
- Max input
- 750 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 50 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Crest FBN0751 in practice
The FBN0751 is the entry of the Crest FB(N,L)0751-6001 range, the smallest of Lochinvar's wave fire-tube commercial boilers. The I&O ratings table (Models 751-6001, Series 100-101 & 110-111) lists 50 to 750 MBH input with 722 MBH gross output and a 626 MBH AHRI net water rating, and the same manual prints 15:1 turndown for the 0751.
The boiler connects on 3" pipe outlet and inlet with a 1-1/4" gas inlet, holds 73 gallons of water, and uses 6" air and 6" vent with stainless steel, polypropylene, PVC or CPVC materials to 100 equivalent feet per the product-page feature list. Weight with water is 1,768 lb per the ratings table, and the family page carries the 8" LCD touchscreen SMART TOUCH control with CON·X·US and a 10-year heat exchanger warranty.
Best suited to
- Commercial projects whose design-day load sits at the bottom of the Crest range
- Plants wanting the 50 MBH minimum fire at 750 MBH ceiling
- Buildings that can commit to 3" boiler piping and 6" air/vent openings
Applicability and support
- Model number
- FBN0751
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 50 MBH | Per the I&O ratings table. |
| Heating input, maximum | 750 MBH | Per the I&O ratings table. |
| Output | ||
| Gross output | 722 MBH | Per the I&O ratings table. |
| Net AHRI water rating | 626 MBH | Per the I&O ratings table. |
| Venting and air | ||
| Air size | 6" | Per the I&O ratings table. |
| Vent size | 6" | Per the I&O ratings table. |
| Venting | Category IV sealed combustion; stainless steel, polypropylene, PVC or CPVC venting | Up to 100 equivalent feet per the Crest product-page feature list. |
| Physical and connections | ||
| Water content | 73 gal | Per the I&O ratings table. |
| Pipe outlet connection | 3" | Per the I&O ratings table. |
| Pipe inlet connection | 3" | Per the I&O ratings table. |
| Gas connection | 1-1/4" | Per the I&O ratings table. |
| Weight with water | 1,768 lb | Per the I&O ratings table. |
Manuals
Alerts documented for this model
- Gas Pressure SW Open
- Low Water Cutoff Open
- Blocked Drain SW Open
- APS Open
- Anti-cycling
- Flame Failure
- Flame Fail Running
- Gas Valve / Relay Failure
- Auto Reset High Limit
- Manual Reset High Limit Open
- Fan Speed Low
- Fan Speed High
- Louver Proving Sw Open
- Flue Temp High
- Delta T High
- Outlet Temp High
- Parameter Programming Complete
- Sensor Open
- Sensor Shorted
- Flue Sensor Open
- Flue Sensor Shorted
- Too Many Resets - Try Later
- Internal Fault
- Flue Temp Shutdown
- Delta T Shutdown
- Outlet Temp Shutdown
- Writing/Programming EEProm Error
- CRC Parameter Error
- Wrong Error Code
- Flame Sense Out of Sequence 1
- Flame Sense Out of Sequence 2
- Flue Damper Switch Open
- IO Expander Out Error
- Failure ADC Controller
- Outlet Sensor Differential
- Flue Sensor Differential
Frequently asked questions
What are the FBN0751's ratings?
50 to 750 MBH of input with 722 MBH gross output and a 626 MBH AHRI net water rating per the I&O ratings table, at 15:1 turndown per the I&O.
What connections does the FBN0751 use?
3" pipe outlet and inlet, a 1-1/4" gas inlet, and 6" air and vent sizes, with a 73-gallon water content and 1,768 lb weight with water per the ratings table.
Questions about the Lochinvar Crest FBN0751?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Lochinvar Crest FBN0751 vs FBN1001Comparison
- Lochinvar Crest FBN1001Same series
- Lochinvar Crest FBN1251Same series
- Lochinvar Crest FBN1501Same series
- Lochinvar Crest FBN1751Same series
- Lochinvar Crest FBN2001Same series
- Lochinvar Crest FBN2501Same series
- Lochinvar Crest FBN3001Same series
- Lochinvar Crest FBN3501Same series
- Lochinvar Crest FBN4001Same series
- Lochinvar Crest FBN5001Same series
- Lochinvar Crest FBN6001Same series
- Lochinvar Crest FCB1000Same series
- Lochinvar Crest FCB1500Same series
- Lochinvar Crest FCB2000Same series
- Lochinvar Crest FCB2500Same series
- Lochinvar Crest FCB3000Same series
- Lochinvar Crest FCB4000Same series
- Lochinvar Crest FCB5000Same series
- Lochinvar Crest FCB6000Same series
- Crest (FB / Hellcat FCB) series hub