Lochinvar · Crest (FB / Hellcat FCB)
Lochinvar Crest FCB4000
The Crest with Hellcat FCB4000 fires 200 to 3999 MBH with 3843 MBH gross output and a 3342 MBH AHRI net rating at 96% thermal efficiency per its product page, with 12" air and vent.
Key figures
- Max input
- 3,999 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 200 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Crest FCB4000 in practice
The FCB4000 is the default model page for the Crest with Hellcat line and the size whose spec block Boilers.ca quotes: the page headlines 96.0% thermal efficiency (spec block 96%) with 20:1 turndown, an ASME H stamp, a 201-gallon nominal capacity, 4" water connections, voltages to 480 and a 10-year heat exchanger warranty. The I&O ratings table lists 200 to 3999 MBH input with 3843 MBH gross output and a 3342 MBH AHRI net water rating, with a 2-1/2" gas inlet and 12" air and vent.
The page describes RealTime O2 Trim as a combustion feature using feedforward and feedback data to deliver a targeted combustion O2 range, controlled from a full-color 10" capacitive touchscreen, and lists the vent type as room air/direct vent or common vent in stainless steel, polypropylene, PVC or CPVC to 150 equivalent feet. The 79.5" height, 43.25" width and 3,874 lb shipping weight come from the same product-page spec block, while the ratings table prints a 5,200 lb weight with water.
Best suited to
- Central plants whose load approaches 4.0 million BTU/hr on the Hellcat platform
- Projects wanting the FCB4000's documented 96.0% thermal efficiency headline
- Designs planned around 12" air and vent openings with 480 V service
Applicability and support
- Model number
- FCB4000
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 200 MBH | Per the I&O ratings table. |
| Heating input, maximum | 3,999 MBH | Per the I&O ratings table. |
| Output | ||
| Gross output | 3,843 MBH | Per the I&O ratings table. |
| Net AHRI water rating | 3,342 MBH | Per the I&O ratings table. |
| Efficiency | ||
| Efficiency (thermal) | 96 % | 96% thermal efficiency per the FCB4000N product-page spec block; the page headline prints 96.0%. |
| Venting and air | ||
| Air size | 12" | Per the I&O ratings table. |
| Vent size | 12" | Per the I&O ratings table. |
| Venting | Category IV sealed combustion; room air/direct vent/common vent in stainless steel, polypropylene, PVC or CPVC | Up to 150 equivalent feet per the Crest with Hellcat product-page feature list. |
| Physical and connections | ||
| Water content | 201 gal | Per the I&O ratings table. |
| Pipe outlet connection | 4" | Per the I&O ratings table. |
| Pipe inlet connection | 4" | Per the I&O ratings table. |
| Gas connection | 2-1/2" | Per the I&O ratings table. |
| Weight with water | 5,200 lb | Per the I&O ratings table. |
| Height | 79.5 in | Per the Lochinvar product page. |
| Width | 43.25 in | Per the Lochinvar product page. |
Manuals
Alerts documented for this model
- Gas Pressure SW Open
- Low Water Cutoff Open
- Blocked Drain SW Open
- APS Open
- Anti-cycling
- Flame Failure
- Flame Fail Running
- Gas Valve / Relay Failure
- Auto Reset High Limit
- Manual Reset High Limit Open
- Fan Speed Low
- Fan Speed High
- Louver Proving Sw Open
- Flue Temp High
- Delta T High
- Outlet Temp High
- Parameter Programming Complete
- Sensor Open
- Sensor Shorted
- Flue Sensor Open
- Flue Sensor Shorted
- Too Many Resets - Try Later
- Internal Fault
- Flue Temp Shutdown
- Delta T Shutdown
- Outlet Temp Shutdown
- Writing/Programming EEProm Error
- CRC Parameter Error
- Wrong Error Code
- Flame Sense Out of Sequence 1
- Flame Sense Out of Sequence 2
- Flue Damper Switch Open
- IO Expander Out Error
- Failure ADC Controller
- Outlet Sensor Differential
- Flue Sensor Differential
Frequently asked questions
What is the FCB4000's efficiency rating?
The FCB4000N product page headlines 96.0% thermal efficiency and its spec block prints 96%; the boiler carries an ASME H stamp and 20:1 turndown per the page copy.
What are the FCB4000's ratings?
200 to 3999 MBH of input with 3843 MBH gross output and a 3342 MBH AHRI net water rating per the I&O ratings table, with a 201-gallon water content.
Questions about the Lochinvar Crest FCB4000?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Lochinvar Crest FCB3000 vs FCB4000Comparison
- Lochinvar Crest FBN0751Same series
- Lochinvar Crest FBN1001Same series
- Lochinvar Crest FBN1251Same series
- Lochinvar Crest FBN1501Same series
- Lochinvar Crest FBN1751Same series
- Lochinvar Crest FBN2001Same series
- Lochinvar Crest FBN2501Same series
- Lochinvar Crest FBN3001Same series
- Lochinvar Crest FBN3501Same series
- Lochinvar Crest FBN4001Same series
- Lochinvar Crest FBN5001Same series
- Lochinvar Crest FBN6001Same series
- Lochinvar Crest FCB1000Same series
- Lochinvar Crest FCB1500Same series
- Lochinvar Crest FCB2000Same series
- Lochinvar Crest FCB2500Same series
- Lochinvar Crest FCB3000Same series
- Lochinvar Crest FCB5000Same series
- Lochinvar Crest FCB6000Same series
- Crest (FB / Hellcat FCB) series hub
- Buying guide
Sources and verification
- Lochinvar — Crest with Hellcat (FCB4000N) model page · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.